ABB SACE Emax 2 Series Operating Instructions Manual page 226

Low voltage air circuit-breaker
Table of Contents

Advertisement

Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply , either on the
Power supply Ekip Com Modbus TCP is supplied directly by the Ekip Supply module to which it is connected.
Interface the module has three signaling leds:
223 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Figure 132
LED
Description
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
Power
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent
Indicates the communication state:
Link (1)
• Off: incorrect connection, signal absent
• on fixed: correct connection
Indicates the communication state:
Activity (2)
• off: no activity on the line
• flashing (activity on line present receiving and/or transmitting)
2
ABB | SACE Emax 2
1
External electronic accessories
5 - Ekip Com Modbus TCP