Zone selectivity With the Zone Selectivity function:
Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply , either on the
Power supply Ekip Link is supplied directly by the Ekip Supply module to which it is connected.
Interface the module has three signaling leds:
237 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
• the IP addresses entered refer to actors with the role of interlock with respect to the current role
• the protections for which selectivity must be actuated by setting a mask, must be selected for each
interlock actor entered. Thus set, the function will now be indicated as logic in the following text so
as to distinguish it from the standard function, now also indicated as hardware in the following text
• thus selected, the protections add to those of the hardware S, I, 2I, MCR, G, D-Backward and D-Forward
• hardware selectivity only, or both hardware and logic selectivity can be selected
• diagnosis can be set, for each interlock release, to ascertain whether there is consistency between
the hardware and logic selectivity information
• a mask can be set for the purpose of identifying those protections whose received selectivity
information must be re-transmitted, regardless of whether the actor is in the alarm status. The
mask is only applicable to logic selectivity information
For further details about the Zone Selectivity function with Ekip Link , please consult page 93.
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Figure 136
LED
Description
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
Power
on and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
per second): module on and communication with Trip unit absent
Indicates the communication state:
Link (1)
• Off: incorrect connection, signal absent
• on fixed: correct connection
Indicates the communication state:
Activity (2)
• off: no activity on the line
• flashing (activity on line present receiving and/or transmitting)
2
ABB | SACE Emax 2
1
External electronic accessories
9 - Ekip Link