ABB SACE Emax 2 Series Operating Instructions Manual page 236

Low voltage air circuit-breaker
Table of Contents

Advertisement

Models Two different modules compatible with the IEC 61850 protocol are available: Ekip Com IEC 61850 and Ekip
Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply , either on the
Power supply Ekip Com IEC 61850 is supplied directly by the Ekip Supply module to which it is connected..
Interface the module has three signaling leds:
233 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Com IEC 61850 Redundant .
The modules are identical in terms of characteristics and installation methods, except for: display menus,
cabling and addresses for system communication, which are specific for each module.
NOTE: if different indications are not given, the information in the next chapter is valid for
both models
The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the
unit (e.g. for applications where high grid reliability is required).
IMPORTANT: each Ekip Touch can be fitted with only one module per type. The configuration
with two modules of the same model is not allowed (example: two Ekip Com IEC 61850
Redundant)
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Figure 135
LED
Description
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module
Power
on and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
per second): module on and communication with Trip unit absent
Indicates the communication state:
Link (1)
• Off: incorrect connection, signal absent
• on fixed: correct connection
Indicates the communication state:
Activity (2)
• off: no activity on the line
• flashing (activity on line present receiving and/or transmitting)
2
ABB | SACE Emax 2
1
External electronic accessories
8 - Ekip Com IEC 61850