ABB SACE Emax 2 Series Operating Instructions Manual page 253

Low voltage air circuit-breaker
Table of Contents

Advertisement

Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
250 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
Parameter
Description
With dead busbar and generator:
• Reversed = Ekip Synchrocheck /external contacts connected to the
Dead bar
generator
configuration
• Normal = Ekip Synchrocheck /external contacts connected to the
grid
Enables automatic synchronism control to be activated:
Auto Live-dead
• Manual = Ekip Touch considers the Dead bar option parameter
detect
• Automatic = Ekip Touch automatically assesses the configuration
to be actuated between the dead busbar and active busbar
Configuration for detecting dead busbar:
• Manual = Ekip Touch considers the Dead bar configuration
Auto Deadbar
parameter
detect
• Automatic = Ekip Touch automatically assesses the configuration
to be actuated between: Reversed and Normal
Rated voltage Un of installation; the value is given as absolute value
Primary voltage
(V) and can be set within the range: 100 V to 1150 V in variable steps.
Secondary voltage of the transformer; the value is given as absolute
Secondary voltage
value (V) and can be set within the range: 100 V to 120 V in variable
steps.
Line-to-line voltage entering the module among the 3 installation
Concatenated Ref
voltages
Defines the rest status of the contact with synchronism not present
Contact Type
between: open (NO) and closed (NC)
parameter not available with busbar active and Auto deadbar detect= Manual
(1)
(2)
with dead busbar and configuration: Reversed, the roles of the internal and external voltages are
reversed
(3)
10% hysteresis is applied to the minimum voltage condition: once reached, the condition is lost if
the voltage drops below 90% of the set limit
parameter not available with dead busbar and Auto deadbar detect= Manual
(4)
NOTE: all the thresholds have ±10% tolerance with the exception of:
• Voltage Delta; the tolerance is the higher value between: ±10% of the set threshold and 0.5%
Un (with Un > 220 V) or 1% Un (with Un ≤ 220 V)
• Frequency Delta; the tolerance is the higher value between ±10% of the set threshold and
0.02 Hz
communication:
Parameter
Description
Frequency
Activates (ON) or deactivates (OFF) frequency control for synchronism
check
assessment
Activates (ON) or deactivates (OFF) phase control for synchronism
Phase check
assessment
Activates (YES) or deactivates (NO) circuit-breaker open status control for
Evaluate CB
synchronism assessment
status
NOTE: fourth synchronism condition with busbar active; second
synchronism condition with dead busbar
With active busbar, minimum time within which the Delta Phase condition
must be obtained
The value is given in seconds and can be set within the range: 100 ms to 3
s, in 10 ms steps
Minimum
NOTE: this is not a synchronism condition, but a parameter allowing
matching
a discrimination to be made between correct and incorrect
time
combinations of the Delta Frequency and Delta Phase conditions.
Owing to worst case latencies, the time that effectively elapses
before synchronism is recognized may be longer than the set time
(approx. 20 ms)
ABB | SACE Emax 2
Default
Standard
Manual
Manual
100 V
100 V
U12
NO
Default
ON
ON
NO
100 ms
External electronic accessories
12 - Ekip Synchrocheck