8.
Extract the disconnection crank from its housing See Figure 93.
9.
Press the lock pushbutton and fit the handle into the moving part. In this phase, the moving part
will still be in the DISCONNECT position. See Figure 94.
Figure 93
10. Turn the crank clockwise until the pushbutton comes out and the indicator shows that the circuit-
breaker is in TEST position. See Figure 95.
Figure 95
11. Press lock pushbutton and turn handle clockwise until pushbutton projects and signaling device
indicates that circuit-breaker is in position CONNECT. See Figure 96.
Figure 96
Figure 94
2
ABB | SACE Emax 2
1
2
1
Continued on the next page
Mechanical characteristics
2 - E2.2-E4.2-E6.2 description