ABB SACE Emax 2 Series Operating Instructions Manual page 210

Low voltage air circuit-breaker
Table of Contents

Advertisement

Replacement The Measurement module can be replaced on its Trip unit, for details consult document 1SDH001000r0528.
207 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
About The About-Modules menu contains the specific menu of the module with the serial number and version
of the module itself.
Test The Measurement module must be disconnected from Ekip Touch (according to the procedure available
on the front label) and the external sockets must be disconnected from the terminal box in the following
cases:
Test
Dielectric test
Isolation between phases
disconnection to be performed also in the presence of Ekip Touch without Measuring package
(1)
If the Measurement module is replaced, module change is indicated on the display by an alarm in the
diagnosis bar when the apparatus is powered for the first time.
To install the new module:
• Confirm the installation module which appears automatically on the display
• Execute manual control, available in the Settings menu (page49)
WARNING! if the Class 1 Power & Energy Metering package is present, module replacement
could impair the performance values indicated on page 120; consult ABB to assess
solutions able to comply with your requirements
Module Measurement ena-
bler
(1)
x
ABB | SACE Emax 2
Module Measurement ena-
bler with voltage sockets
x
x
Internal electronic accessories
2 - Measurement