ABB SACE Emax 2 Series Operating Instructions Manual page 79

Low voltage air circuit-breaker
Table of Contents

Advertisement

D Protection
t
I7
t7bw
t7fw
76 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Function
D protection is very similar to S protection, with the additional capability of recognizing the direction of
the current during a fault.
D
The current direction allows the user to find out whether the fault is on the supply side or load side of the
device controlled by Ekip Touch.
In ring type distribution systems, D protection allows the distribution section in which the fault has
occurred to be identified and disconnected without affecting the rest of the installation (using zone
selectivity).
I
Depending on the direction of the fault, if the current of one or more phases exceeds threshold I7 (I7fw or
I7bw) for longer than time t7 (t7fw or t7bw), the protection activates and sends a TRIP command.
The fault direction is established by comparing the detected fault current with the reference direction.
NOTE: the reference direction is calculated considering the set value of the power flow
direction and the phase sequence (cyclic direction of the phases):
Phase sequence (set) Power flow (set)
123
123
123
123
321
321
321
321
To check and simulate the trip times in relation to all the parameters, please consult:
• the summary table of the protections with the calculation formulas (page 95)
• the graph with trip curve (page 109)
Parameter
Description
Activates/deactivates the protection and its availability in the
Enable
parameters menu
Activates/deactivates transmission of the open command: if disabled,
Trip Enable
the alarm and exceedance of protection time are only managed as
information
Establishes the value that activates the protection with forward
Threshold I7
direction.
Fw
The value is given as both absolute value (amperes) and relative value
(In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
Establishes the value that activates the protection with backward
Threshold i7
direction.
Bw
The value is given as both absolute value (amperes) and relative value
(In) and can be set within the range: 0.6 In to 10 In, in 0.1 In steps
This is the trip time in the case of forward direction.
Time t7 Fw
The value is given in seconds and can be set within the range: 0.1 s to
0.8 s, in 0.01 s steps
This is the trip time in the case of backward direction.
Time t7 Bw
The value is given in seconds and can be set within the range: 0.1 s to
0.8 s, in 0.01 s steps
Activates/deactivates the function and selectivity time availability on
the display.
ZoneSelectivity
(1)
This is the trip time of the protection with the zone selectivity function
Selectivity
activated, forward direction and selectivity input Fw not present.
time Fw
(1)
The value is given in seconds and can be set within the range: 0.1 s to
0.8 s, in 0.01 s steps
This is the trip time of the protection with the zone selectivity function
Selectivity
activated, backward direction and selectivity input Bw not present.
time Bw
The value is given in seconds and can be set within the range: 0.1 s to
(1)
0.8 s, in 0.01 s steps
High-->Low
Bottom --> Top
High-->Low
Bottom --> Top
High-->Low
Bottom --> Top
High-->Low
Bottom --> Top
NOTE: configure selectivities S, S2, I, 2I, MCR and G OFF to ensure
that selectivity D functions correctly
NOTE: configure selectivities S, S2, I, 2I, MCR, G, Gext and
MDGF OFF to ensure that selectivity D functions correctly
Phase sequence (de-
Reference direction
tected)
(forward direction)
123
High-->Low
123
Bottom --> Top
321
Bottom --> Top
321
High-->Low
123
Bottom --> Top
123
High-->Low
321
High-->Low
321
Bottom --> Top
Continued on the next page
Ekip Touch - Protections
ABB | SACE Emax 2
Default
OFF
ON
2 In
2 In
0,2 s
0,2 s
OFF
0,13 s
0,13 s
6 - Power protections