ABB SACE Emax 2 Series Operating Instructions Manual page 234

Low voltage air circuit-breaker
Table of Contents

Advertisement

Information in menu The following information will be available in the About - Modules menu if Ekip Touch has detected the
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
231 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
module correctly:
Information
Description
SN and version
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
IP address
can be set via the menu in the event of a static IP
NOTE: without a DHCP server, the module automatically adopts a random
IP address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the
Network Mask
modules belong and enables modules to be searched for within a defined set
of recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal
MAC address
to ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
communication:
Parameter
Description
Enable IEEE
Allows the IEEE 1588 protocol for distribution of the clock and
1558
synchronization signal to be enabled
IEEE 1558
Enables the module to be set up as a master in the the network
Master
segment to which it belongs (synchronization clock).
IEEE 1558 Delay
Allows the data exchange mode between module and master,
mechanism
either Peer-to-Peer or End-to-End, to be selected.
Enable client
Allows the SNTP protocol for distribution of the clock and
SNTP
synchronization signal to be enabled
ANTP Server
Allows the network server that supplies the SNTP to be set.
address
Time zone
Defines the time zone to be used for synchronism
Daylight Saving
Used to select whether daylight saving time is present (ON) or
Time
not (OFF) in the country to which the synchronization time refers
Parameter useful if an IEEE 1588 GrandMaster clock is not
available:
• If enabled (ON), the module is seen as an IEEE1588 master
IEEE 1588
clock by all the slaves/devices in the same local network, even
Boundary clock
when the source of external synchronism is different from IEEE
1588 (SNTP for example)
• If disabled (OFF) the module benefits from the synchronism of
the master in its own network
Enable
Enables the Rate limiter function, which limits the number of
package
packages entering the module from the network, to be activated/
Limitation
deactivated
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(1)
communication:
Information
HW and Boot version
Flash CRC status and result
Ekip Link status
SNTP Server Error
SNTP Server Synchronization
IEEE 1558 status
.
(1)
(1)
Description
General module information
Information about the correctness of the SW in the module
Signals Ethernet cable connection errors
Error in communication with SNTP server
State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave
or PTP Master Active) or absence (PTP Master but Passive) of a
higher level master
ABB | SACE Emax 2
Default
OFF
OFF
End-to-End
OFF
0.0.0.0
+00:00
OFF
OFF
Disable
External electronic accessories
7 - Ekip Com EtherNet/IP TM