Compressor Motor Overload Settings & Maximum Vsd Frequency - York YCAV0157 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

MAINTENANCE
COMPRESSOR MOTOR OVERLOAD & MAX. VSD FREQUENCY
TABLE 34 - COMPRESSOR MOTOR OVERLOAD SETTINGS & MAX. VSD FREQUENCY
2 COMP CHILLER MODELS WITH STANDARD (PIN 52 = X) AND ULTRA QUIET (PIN 52 = L) FANS
CHILLER MODEL
CHILLER NAME-
(2 COMP)
PLATE VOLTAGE
W/ STD & UQ FANS
YCAV0157EA/VA
200,230,380,460,575
YCAV0157SA/PA
200,230,380,460,575
YCAV0177EA/VA
200,230,380,460,575
YCAV0177SA/PA
200,230,380,460,575
YCAV0187EA/VA
200,230,380,460,575
YCAV0187SA/PA
200,230,380,460,575
YCAV0197EA/VA
200,230,380,460,575
YCAV0207EA/VA
200,230,380,460,575
YCAV0207SA/PA
200,230,380,460,575
YCAV0227EA/VA
200,230,380,460,575
YCAV0227SA/PA
200,230,380,460,575
YCAV0247EA/VA
200,230,380,460,575
YCAV0247SA/PA
200,230,380,460,575
YCAV0267SA/PA
200,230,380,460,575
302
COMPRESSOR 1
OVERLOAD SETTING
(VAC)
(AMPS)
192
196
184
270
250
254
244
234
247
238
255
289
289
289
FORM 201.21-NM1 (1223)
COMPRESSOR 2
MAXIMUM VSD
OVERLOAD SETTING
FREQUENCY (HZ)
(AMPS)
192
196
197
191
183
198
244
250
273
238
255
238
254
289
JOHNSON CONTROLS
186
200
200
182
192
200
182
192
186
200
200
200
200
200