Compressor Motor Overload Settings & Maximum Vsd Frequency - York YCAV0569 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

MAINTENANCE
COMPRESSOR MOTOR OVERLOAD & MAX. VSD FREQUENCY
TABLE 34 - COMPRESSOR MOTOR OVERLOAD SETTINGS & MAX. VSD FREQUENCY
2 COMP CHILLER MODELS WITH STANDARD (PIN 52 = X) AND ULTRA QUIET (PIN 52 = L) FANS
CHILLER MODEL
(2 COMP)
W/ STD & UQ FANS
YCAV0569EA/VA
YCAV0569SA/PA
YCAV0639EA/VA
YCAV0639SA/PA
YCAV0679EA/VA
YCAV0679SA/PA
YCAV0719EA/VA
YCAV0739EA/VA
YCAV0739SA/PA
YCAV0819EA/VA
YCAV0819SA/PA
YCAV0889EA/VA
YCAV0889SA/PA
YCAV0969SA/PA
270
CHILLER NAME-
COMPRESSOR 1
PLATE VOLTAGE
OVERLOAD SETTING
(VAC)
400
400
400
400
400
400
400
400
400
400
400
400
400
400
COMPRESSOR 2
OVERLOAD SETTING
(AMPS)
(AMPS)
168
168
184
184
173
185
231
164
225
165
238
185
209
209
210
225
215
238
223
223
239
239
283
223
283
238
281
281
FORM 201.21-NM2 (616)
MAXIMUM VSD
FREQUENCY (HZ)
186
200
200
182
192
200
182
192
186
200
200
200
200
200
JOHNSON CONTROLS