Neoprene Isolator Position - York YCAV0157 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

TECHNICAL DATA
ND-X NEOPRENE ISOLATOR SPECIFICATIONS
Steel Plate - Top &
Bottom Neoprene
covered to prevent
corrosion
W
SIZE
D
ND-C
2-9/16
ND-D
3-3/8
ND-DS
3-3/8
ND-C
65.1
ND-D
85.7
ND-DS
85.7
PIN 54 = N
**Weight Range (lbs) **Weight Range (kg)
UP TO 751 LBS
751-1651 LBS
1651-3226 LBS
** Value is de-rated by 15%
INSTALLATION OF NEOPRENE MOUNTS
It is not neccesary to bolt the mountings to a concrete pad in most cases. Mountings should always be bolted to the
chiller rails. When mountings and the chiller are installed on steel framing above the ground, the mountings should
be bolted to the steel framework. Lower the chiller on to the mountings evenly to avoid placing excessive weight
on individual isolators.
130
D
H
T
ENGLISH
H
L
2-3/4
5-1/2
1/4
2-3/4
6-1/4
5/16
2-3/4
6-1/4
5/16
69.9
139.7
6.4
69.9
158.8
7.9
69.9
158.8
7.9
Up to 341 kg
341 to 749 kg
749 to 1463 kg
"CS" Cap Screw
"MBD" Max. Bolt Dia.
BC
T
W
BC
2-5/16
4-1/8
4
5
4
5
SI
58.7
101.9
101.6
127.0
101.6
127.0
COLOR
YORK P/N
ND-C
Yellow
ND-D
Yellow
ND-E
Yellow
FORM 201.21-NM1 (1223)
L
CS
MBD
1/2-13x1"
1/2"
1/2-13x1"
1/2"
1/2-13x1"
1/2"
1/2-13x1"
13
1/2-13x1"
13
1/2-13x1"
13
YORK P/N
029-24584-001
029-24584-002
029-24584-003
JOHNSON CONTROLS
LD10569

Advertisement

Table of Contents
loading