MICRO PANEL
The values displayed under each of the key presses may
be changed by keying in new values and pressing the
(ENTER) key to store the new value into memory.
Where more than one value may be keyed in on a dis-
play, a portion of the data that does not need updating
may be skipped by pressing the (ENTER) key. The
(ENTER) key must also be pressed after the last value
in the display to store the data into memory.
The ▲ (ARROW) key allows scrolling back through
the setpoints displays.
The minimum, maximum, and default values allowed
under the SETPOINTS key are provided in TABLE
16, below:
TABLE 16 - SETPOINT LIMITS
PROGRAM VALUE
Leaving Chilled Liquid Setpoint
Leaving Chilled Liquid Control Range
Max. Remote Temperature Reset
246
SETPOINTS KEY (CON'T)
MODE
Water Cooling
Glycol Cooling
-
-
LOW LIMIT
HIGH LIMIT
40.0°F
60.0°F
4.4°C
15.6°C
15.0°F
70.0°F
-9.4°C
15.6°C
1.5°F
2.5°F
0.8°C
1.4°C
2°F
40°F
1°C
22°C
FORM 201.21-NM1 (1223)
DEFAULT
44.0°F
6.7°C
44.0°F
6.7°C
2.0°F
1.1°C
20°F
11°C