York YCAV0157 Installation Operation & Maintenance page 120

Air-cooled screw liquid chillers
Table of Contents

Advertisement

TECHNICAL DATA
DIMENSIONS - YCAV0267S/P Standard Efficiency SI
102
POWER ENTRY IS ON BOTTOM OF PANEL
Notes:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable
operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable air
flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pressure safety
cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m;
top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.
120
38
POWER ENTRY
254 WIDE X 330 HIGH
VIEW B-B
C
B
C C
540
161 (EDGE OF
UNIT TO COOLER
CONNECTION)
CONTROL ENTRY
76 WIDE X 343 HIGH
44
B
2239
VIEW A-A
FORM 201.21-NM1 (1223)
305
VIEW C-C
LD10572A
JOHNSON CONTROLS