York YCAV0157 Installation Operation & Maintenance page 235

Air-cooled screw liquid chillers
Table of Contents

Advertisement

The next key press displays the current limit values set
locally on the panel under the PROGRAM key, remotely
by an ISN, and remotely by the Current Limit input.
Any current limits that are inactive will display "XXX"
instead of a numeric value.
VSD CURRENT LIMIT
ISN = XXX
The next key press displays DC bus voltage for 2 and 3
compressor units.. On 4 compressor units, the 2nd mes-
sage will apply, since two DC bus voltages are present
(Systems 1/3 and 2/4).
VSD
DC BUS VOLTAGE = XXX VDC
VSD DC BUS VOLTAGES BUS 1 = XXX VDC
The next key press displays the Control Panel/VSD
Internal Ambient Temperature and VSD Cooling Pump/
Fan Status. YYY will indicate ON or OFF.
VSD
INTERNAL AMBIENT TEMP = XXX.X °F
COOLING SYSTEM STATUS = YYY
The next key press displays the IGBT highest baseplate
temperature for 2 and 3 compressor units. 4 compres-
sor units display temperatures for Systems 1/3 (T1) and
Systems 2/4 (T2).
VSD IGBT BASEPLATE TEMPS
The next key press displays the state of the Precharge
signal, where XXX is either ON or OFF. The first dis-
play is for 2 and 3 compressor units, the second display
shown is for 4 compressor units where Precharge 1 is
for compressors 1 and 3 DC Bus and Precharge 2 is for
compressors 2 and 4 DC Bus.
VSD
PRECHARGE SIGNAL = XXX
VSD
PRECHARGE 1 SIGNAL = XXX
VSD
PRECHARGE 2 SIGNAL = XXX
JOHNSON CONTROLS
VSD DATA KEY (CON'T)
LOCAL = XXX %FLA
REMOTE = XXX %FLA
BUS 2 = XXX VDC
T1 = XXX °F
T2 = XXX °F
The next key press displays the setting of the VSD's
105% FLA overload potentiometer for Compressor #1
and 2. The settings are determined by the adjustment of
the overload potentiometers on the VSD Logic Board.
These pots are factory set and should not require chang-
ing unless the circuit board is replaced. See TABLE 34
for factory settings.
VSD
COMP 1 MOTOR OVERLOAD = XXX AMPS
COMP 2 MOTOR OVERLOAD = XXX AMPS
The next key press displays the setting of the VSD's
105% FLA potentiometer for Compressor #3 and #4 (3
and 4 compressor units only). The second line will be
blanked out on 3 compressor units.
VSD
COMP 3 MOTOR OVERLOAD = XXX AMPS
COMP 4 MOTOR OVERLOAD = XXX AMPS
FORM 201.21-NM1 (1223)
8
235

Advertisement

Table of Contents
loading

Table of Contents