Operating Data Printout - York YCAV0157 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

MICRO PANEL
A sample of the operating data printout is shown below.
The operating data printout is a snapshot of current
system operating conditions when the printout was se-
lected. The sample shows combined printouts of 2, 3,
and 4 circuit units. The actual printout will only show
data for the appropriate chiller type.
Bold italic text below a line of print is
not on the actual printout. Bold italic
text indicates information that may
not be available on all printouts or is
additional information to help explain
the difference in a 2/3 or 4-circuit
printout.

OPERATING DATA PRINTOUT

YORK INTERNATIONAL CORPORATION
LATITUDE SCREW CHILLER
OPERATING DATA
2:04:14 PM
SYS 1
NOT RUNNING
SYS 2
COMPRESSOR RUNNING
OPTIONS
CHILLED LIQUID
LOCAL/REMOTE MODE
LEAD/LAG CONTROL
REMOTE TEMP RESET
REMOTE CURRENT LIMIT
REMOTE SOUND LIMIT
(if Sound Limiting enabled)
LOW AMBIENT CUTOUT
PROGRAM VALUES
SUCT PRESS CUTOUT
LOW AMBIENT CUTOUT
LEAVING LIQUID CUTOUT
MOTOR CURRENT LIMIT
PULLDOWN CURRENT LIMIT
PULLDOWN LIMIT TIME
SUCTION SUPERHEAT SETP
UNIT ID NUMBER
SOUND LIMIT SETPOINT
(if Sound Limiting enabled)
UNIT DATA
LEAVING LIQUID TEMP
RETURN LIQUID TEMP
TEMP RATE
COOLING RANGE
REMOTE SETPOINT
AMBIENT AIR TEMP
LEAD SYSTEM
FLOW SWITCH
EVAPORATOR PUMP RUN
EVAPORATOR HEATER
ACTIVE REMOTE CONTROL
260
PRINT KEY (CON'T)
18 JUN 05
W
A
T
E
R
R E M O T E
A U T O M A T I C
D I S A B L E D
0
T O
1 0
V
4 TO 20 MA
E N A B L E D
4 4
P S I G
2 5 . 0
D E G F
3 6 . 0
D E G F
1 0 0
% F L A
1 0 0
% F L A
0 MIN
1 2 . 0
D E G F
0
1 0 0 %
4 9 . 0
D E G F
5 8 . 2
D E G F
X X X . X
D E G F / M I N
4 2 . 0 + / - 2 . 0
D E G F
4 4 . 0
D E G F
7 4 . 8
D E G F
SYS 2
O N
O N
O F F
N O N E
O P E R A T I N G
H O U R S
(3 circuit)
START COUNTER
(3 circuit)
(4 circuit)
SOFTWARE VERSION
VSD DATA
ACTUAL FREQUENCY
COMMAND FREQUENCY
DC BUS VOLTAGE
(2 circuit & 3 circuit)
DC BUS VOLTAGES
(4 circuit)
INTERNAL AMBIENT TEMP
COOLING SYSTEM STATUS
BASEPLATE TEMPS
PRECHARGE SIGNAL
(2 circuit & 3 circuit)
PRECHARGE SIGNALS
(4 circuit)
MOTOR OVERLOADS 1/2
MOTOR OVERLOADS 3/4
(3 circuit & 4 circuit)
SOFTWARE VERSION
SYSTEM 1 DATA
COMPRESSOR STATUS
RUN TIME
MOTOR CURRENT
0 AMPS
SUCTION PRESSURE
DISCHARGE PRESSURE
OIL PRESSURE
SUCTION TEMPERATURE
DISCHARGE TEMPERATURE
OIL TEMPERATURE
SAT SUCTION TEMP
SUCTION SUPERHEAT
SAT DISCHARGE TEMP
DISCHARGE SUPERHEAT
MOTOR TMP
XXX.X
XXX.X
COMPRESSOR SPEED
ECONOMIZER SOLENOID
FLASH TANK LEVEL
FEED VALVE % OPEN
DRAIN VALVE % OPEN
CONDENSER FANS ON
COMPRESSOR HEATER
RUN PERMISSIVE
VSD RUN RELAY
VSD SOFTWARE RUN SIGNAL
SYSTEM 2 DATA
COMPRESSOR STATUS
RUN TIME
MOTOR CURRENT
104 AMPS
SUCTION PRESSURE
DISCHARGE PRESSURE
OIL PRESSURE
SUCTION TEMPERATURE
DISCHARGE TEMPERATURE
OIL TEMPERATURE
SAT SUCTION TEMP
SUCTION SUPERHEAT
SAT DISCHARGE TEMP
DISCHARGE SUPERHEAT
FORM 201.21-NM1 (1223)
1 = X X X X X ,
2 = X X X X X
3=XXXXX
3 = X X X X X ,
4 = X X X X X
1 = X X X X X ,
2 = X X X X X
3=XXXXX
3 = X X X X X ,
4 = X X X X X
C . A C S . X X . 0 0
X X X . X
H Z
X X X . X
H Z
X X X
V D C
XXX XXX VDC
X X X . X
D E G F
X X X
XXX XXX DEGF
X X X
X X X
X X X
XXX XXX AMPS
XXX XXX AMPS
C.VSD.XX.00
O F F
0- 0- 0- 0 D-H-M-S
0
% F L A
1 2 5
P S I G
1 3 1
P S I G
1 3 0
P S I G
6 8 . 4
D E G F
6 8 . 8
D E G F
6 8 . 8
D E G F
7 1 . 8
D E G F
3 . 4
D E G F
7 4 . 5
D E G F
6 . 3
D E G F
XXX.X
D E G F
XXX.X %
O F F
XXX.X %
XXX.X %
XXX.X %
0
O N
O N
O F F
O F F
O N
0-0-15-26 D-H-M-S
8 7
% F L A
5 7
P S I G
2 3 3
P S I G
2 1 8
P S I G
4 2 . 9
D E G F
1 4 5 . 5
D E G F
1 0 2 . 8
D E G F
3 1 . 7
D E G F
1 1 . 2
D E G F
1 1 2 . 1
D E G F
3 3 . 4
D E G F
JOHNSON CONTROLS