Fig 35 - Standard Iplv Fan Control; Fig 36 - High Iplv Fan Control - York YCAV0157 Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

OPERATION
Fan on and off control points will vary for standard
and optional optimized IPLV chillers. Unless controls
dictate all fans running due to high VSD ambient tem-
peratures, fans will sequence on when a compressor
runs and discharge pressure rises. During compressor
ramp up or ramp down when compressors are staged,
the current fan stage will be held.
The number of fans is factory programmable under the
password protected Unit Setup Mode.
Standard IPLV Fan Control
Fan staging ON and OFF points will be determined
by the ambient temperature. The fan stage will be
incremented, unless the 5 second timer between fan
stages is still timing when the discharge pressure rises
above the Fan ON Press. The fan stage is decremented,
unless the 5 second timer between fan stages is still
timing when the discharge pressure falls below the Fan
OFF Press. When a fan stage is incremented, the fan
delay timer is set to 5 seconds, and the Fan ON pressure
is ramped 20 PSIG over the original ON point back to
the original value over the next 20 seconds. When a
fan stage is decremented, the fan delay timer is set to 5
seconds, and the Fan OFF pressure is ramped 20 PSIG
below the original Fan OFF point, back to the origi-
nal value over the next 20 seconds. The ON and OFF
points will vary as ambient temperature changes. FIG.
35 below shows the fan ON and OFF points relative to
ambient temperature.
Standard IPLV Fan Control
190
180
170
160
150
140
130
120
110
100
90
75
85
95
105
Ambient Air Temp (°F)
FIG. 35 - STANDARD IPLV FAN CONTROL
190
CONDENSOR FAN CONTROL (CON'T)
Fan On Press
Fan Off Press
`
115
125
LD10633
Optimized IPLV Fan Control
Fan staging on and off points will be determined by the
ambient temperature. The fan stage will be incremented,
unless the 5 second timer between fan stages is still
timing when the discharge pressure rises above the Fan
ON Press. The fan stage is decremented, unless the 5
second timer between fan stages is still timing when
the discharge pressure falls below the Fan OFF Press.
When a fan stage is incremented, the fan delay timer is
set to 5 seconds, and the Fan ON pressure is ramped 20
PSIG over the original ON, point back to the original
value over the next 20 seconds. When a fan stage is
decremented, the fan delay timer is set to 5 seconds,
and the Fan OFF pressure is ramped 20 PSIG below
the original Fan OFF point, back to the original value
over the next 20 seconds. The ON and OFF points will
vary as ambient temperature changes. FIG. 36 below
shows the fan ON and OFF points relative to ambient
temperature.
Optimized IPLV Fan Control
155
150
145
140
135
130
125
120
`
115
110
105
100
95
90
75
85
95
105
Ambient Air Temp (°F)
FIG. 36 - HIGH IPLV FAN CONTROL
High VSD Cabinet Ambient Temperature
Fan Operation
All condenser fans on all systems will run when the
chiller is off and enabled to run, if the VSD internal
ambient temperature is higher than 5°F below the VSD
Cabinet Ambient Temperature Cutout of 158°F (158°F
- 5°F = 153 °F). When the fans turn on in this situa-
tion, the fan outputs will cycle one at a time with a 100
ms delay between fan starts. When the VSD internal
ambient falls below the "Restart Temperature" (158°F
Cutout - 10°F = 148 °F), the fans will all be turned off
without a delay.
FORM 201.21-NM1 (1223)
Fan On Press
Fan Off Press
115
125