The Control/VSD Cabinet contains lethal High AC and DC voltages. Before
performing service inside the cabinet, remove the AC supply feeding the chiller
and verify using a non-contact voltage sensor.
The DC Voltage on the VSD DC Bus will take 5 minutes to bleed off, after AC
power is removed. Always check the DC Bus Voltage with a Voltmeter to assure
the capacitor charge has bled off before working on the system.
• NEVER short out the DC Bus to discharge the filter capacitors.
• NEVER place loose tools, debris, or any objects inside the Control Panel/VSD
Cabinet.
• NEVER allow the Control Panel VSD Cabinet doors to remain open if there is
a potential for rain to enter the panel. Keep doors closed and assure all latches
  are engaged on each door unless the unit is being serviced.
• ALWAYS lockout the disconnect supplying AC to the chiller.
• The 1L Line Inductor will reach operating temperatures of over 300° F. DO
NOT open panel doors during operation. Assure the inductor is cool whenever
working near the inductor with power off.