Operating Data - Remote Printout - York YCAS0098EB Installation Operation & Maintenance

Air-cooled liquid chillers
Hide thumbs Also See for YCAS0098EB:
Table of Contents

Advertisement

Micro Panel Contents
T E M P
E R R O R
T E M P
R A T E
The upper message gives the difference (error) between
actual leaving chilled liquid temperature and the pro-
grammed Target temperature. The lower message gives
the rate of change of the chilled liquid leaving temperature
in degrees per minute. A minus sign (-) indicates falling
temperature. No sign indicates rising temperature.
L E A D
S Y S T E M
S Y S T E M
N U M B E R
This message advises which system is programmed as
the lead.
E V A P
P U M P
E V A P
H E A T E R
This message indicates the position of the optional
auxiliary contacts for the evaporator water pump and
the status of the evaporator heater.
For the evaporator pump contacts, ON = contacts closed,
OFF = contacts open.
The Evaporator Heater status is controlled on ambient
temperature as follows: If measured ambient falls below
40°F (4°C) the Evaporator Heater is switched ON. If
measured ambient then rises above 45°F (7°C) the heater
is switched OFF. The evaporator heater prevents water
standing in the evaporator from freezing.
A C T I V E
R E M O T E
N O N E
This message indicates that a remote device such as a
Remote Control Center, an ISN controller, or another
device sending a PWM signal for temperature or current
reset is overriding control points programmed through
the keypad or default microprocessor setpoints. The
following displays may be encountered:
NONE
No remote control active. Remote
monitoring may be active.
ISN
YorkTalk via ISN or Remote Control
Center (remote mode).
PWM CURR – EMS PWM Current Limiting Enabled
PWM TEMP – EMS PWM Temp. Reset Enabled
CUR/TEMP – EMS PWM Current Limiting &
Temperature Reset Enabled
148
0 0 . 5
° F
-
0 . 9
° F / M
I S
#
I S
O F F
I S
O N
C T R L
System Data:
The following sequence of three displays are provided
first for System 1, then for System 2, and then for Sys-
tems 3 and 4 as applicable.
S Y S
#
R U N
1 -
3 - 4 8 - 1 7
This message displays the accumulated Run Time since
the last start in Days (D), Hours (H), Minutes (M), and
Seconds (S).
S Y S
#
L L S V
E C O N
T X V
S O L
This message indicates the Liquid Line Solenoid Valve
and the economizer TXV solenoid valve position: ON =
Energized/Open, OFF = De-energized/Closed.
S Y S
#
F A N
C O M P
H E A T E R
This message advises the stage of condenser fan oper-
ation on this system and the status of the compressor
heater. See Section 8.4 for details of fan staging.
Once the System Data sequence has been repeated for
the second system, pressing the or key again will
loop back to the beginning to the Load/Unload Timer
display. To leave the sequence at any point press a key
from another section of the keypad.
Pressing the " * " at any time while
in the OPER DATA mode displays the
EPROM software version being used,
as shown below:
S O F T W A R E
C . A 1 4 . 1 0 . 0 1
4.4
OPERATING DATA –
REMOTE PRINTOUT
The follow text shows a typical example printout ob-
tained by pressing the Operating Data key with an op-
tional printer attached. In this case an example is shown
for a YCAS 2 System Chiller.
T I M E
D - H - M - S
I S
O N
I S
O N
S T A G E
3
I S
O N
V E R S I O
No
JOHNSON CONTROLS