Comms Programming; Comms Programming Commands; Set Domestic Number - Bosch Solution 16plus Installation Manual

Hide thumbs Also See for Solution 16plus:
Table of Contents

Advertisement

T
he Solution 16
has a built in dialler that connects directly
plus
to a standard PSTN telephone line. To program the dialler you
must set the telephone number to dial and then the reporting
format to send the information in.
The command menu allows you to set the Domestic Numbers,
initiate a SolutionLink Upload / Download session, turn on/off
call forwarding.
There are two independent reporting routes that define where
a reportable event should be sent, by default all events will
report through route 1. Reportable events in the system are
categorised into Alarm, System, Emergency, Open/Close and
Test. This means that you are able to steer these different event
categories to different report routes. A report route is just like
an independent dialler, it has its own primary and secondary
telephone numbers and reporting format.
Example: Route 1 = CID, Route 2 = SMS
If you set the reporting route for Open/Close as Route 2 and all
other events to Route 1, then all reports will be sent to route 1
in Contact ID format and then all open close reports will be sent
through SMS. This is very handy if you want to monitor what
time your children come home from school or cleaners entering
or leaving your premises.
Telephone numbers can be 32 digits long and characters
0-9 * # and , are supported with the comma representing a 2
second pause. Destination route 1 and route 2 both have their
own Primary and Secondary telephone numbers, Domestic
reporting has 3 telephone numbers and remote access has one
call back number.
There are two back to base monitoring formats called CID and
SIA, both formats are all predefined so the system will always
send the same reporting code for the same event. The type
of zone selected under zone type automatically determines
the reporting code to the base station. If a zone is defined as
Medical then when it goes into alarm the report will be Medical
Alarm, if a zone is programmed as a Fire zone then the report
will automatically be Fire Alarm.
Bosch Security Systems 05/10 BLCC100I

Comms Programming

COMMS P ROGRA MMIN G COMMA NDS
Comms > Commands >

Set Domestic Number

Domestic reporting allows the Solution control panel to send
reports to personal telephone numbers (eg. mobile telephone
numbers). Up to three different telephone numbers can be
programmed, each having a maximum of 32 digits.
Each telephone call needs to be acknowledged by the user that
answers the incoming call. If the user fails to acknowledge the
call, the Solution control panel will make another attempt to
report until the maximum number of call attempts has been
reached. To acknowledge the call, the user needs to press the
[#] key on their telephone.
1)
Enter [MENU] + [5] + [0] + [0]. If the panel has not configured to
report via domestic format, the keypad will display the
following:
Domestic Reports Not
Enabled. Please Contact
Your Security Service
Provider
2)
If the control panel has been configured to report via domestic
format, the keypad will display information for telephone
number 1.
3)
Using the arrow and numeric keys, enter all the digits of the
first telephone number. You can change a single digit in the
number by scrolling the cursor left or right. For special
characters (eg. , = pause * or # etc), use the up and down arrow
keys. To clear all text from the cursor position to the right,
press the [OFF] key.
Domestic Phone Number 1
97417_
Press  0-9 OK to SAVE
4)
When the first number is complete press [OK] to program
telephone number 2 if required.
i
See MENU 5-4-0 and 5-4-1 to configure the Transmission Format
to Domestic Reporting.
Note