Bosch Solution 144 Quick Start Manual
Hide thumbs Also See for Solution 144:
Table of Contents

Advertisement

Solution 144
Security Systems
Quick Start Guide
EN
Security System

Advertisement

Table of Contents
loading

Summary of Contents for Bosch Solution 144

  • Page 1 Solution 144 Security Systems Quick Start Guide Security System...
  • Page 2: Solution 144 Quick Start Guide

    Back to Base reporting, SMS and use of the publication; and (iii) not modify the publication Email Reporting and Automatic Time and Date in any way without the prior written permission of Bosch. Adjustments require a working telephone line to operate and telephone communication service Except as specified above or where authorised by the provider charges are applicable.
  • Page 3: Table Of Contents

    Keypad Tones ..................16 Figure 19: LAN Connection Using Twisted Pair Cable ....11 Keypad & Readers Setup ..............17 Figure 20: Solution 144 Board Layout ..........12 DIP Switch Address Select ..............17 Figure 21: Solution 144 Connection Diagram ........13 Rotary Switch Address Select ............
  • Page 4: Features

    Partitionable To 8 Areas ♦ Dialler Reports SIA, Contact ID, SMS and Email Programming Formats You can program the Solution 144 either by a keypad or ♦ Supervised LAN Keypads (Maximum 16 Keypads) using a personal computer using the Solution Link upload/ ♦...
  • Page 5: About The Panel

    Solution 144 Quick Start Guide Abo ut Th e Pa n el flange of the enclosure and then slide the base of the bracket toward the top until the tamper switch locates in E n c l os ure s the rear of the enclosure.
  • Page 6: Installing Panels And Modules

    3mm machine screws supplied with the enclosure. Note The use of self tapping screws will damage the clips. Figure 3: MW720B - Small Enclosure Details Figure 5: MW720B Configuration Examples Figure 4: PCB Mounting Clip Bosch Security Systems 10/12 BLCC600R...
  • Page 7: Figure 6: Mw730B - Large Enclosure Details

    Solution 144 Quick Start Guide When installing large modules you should fit 5 320 mm mounting clips as shown. Clip 5 provides support under the main terminal block only. No screw is fitted. MODULE CABLE ENTRY (REAR) SPACE 1 CABLE ENTRY (REAR)
  • Page 8: Connecting Power To The Panel

    Error Error Flash Once Every 2 Seconds Flash Fast AC or Battery Trouble Table 3: Status Indicator LED During factory defaulting the Status and Dialler LED indicators will flash alternatively for approximately Note 15 seconds. Bosch Security Systems 10/12 BLCC600R...
  • Page 9: Wiring Diagrams

    Solution 144 Quick Start Guide Wi r i n g D i a gra m s ALARM ZN 1  ZONE 1 ZN 1 ZONE 1 ZONE 2 ZN 2 ZONE 2 ALARM ZN 2 Figure 14: N/O Single EOL Zone...
  • Page 10: Lan Overview

    This terminal is simply a connect the EARTH wire from any 3 wire plug pack to the termination point and is not internally connected. module’s EARTH input terminal, if you have installed a separate communication earth wire. Bosch Security Systems 10/12 BLCC600R...
  • Page 11: System Earthing

    Solution 144 Quick Start Guide System Ear th ing 2.5mm Yellow/Green When running a CET communications Earth as per CONTROL PANEL Connect to main building C. E. T. Figure 19, the communication earth should be connected EARTH earth conductor. to the earth terminal on each module and then connected back through the CET to the main building earth conductor.
  • Page 12: Pcb Layout

    10-Pin Serial Input Connection Socket For Direct Link / Flash Programming etc. Zone Input Terminals Voice Module Connection Socket (Optional) Telephone Line Connection Socket (RJ12 6P4C) Telephone Line Connection Terminals Figure 20: Solution 144 Board Layout Bosch Security Systems 10/12 BLCC600R...
  • Page 13: Connection Diagram

    ZONE 6 Connect +12V ZONE 7 Accessory Power ZONE 8 RJ12 6P4C - RJ12 6P4C Phone Lead Connect To Telephone Line Mode 3  Premises Telephone Incoming Street Telephone Line Figure 21: Solution 144 Connection Diagram Bosch Security Systems 10/12 BLCC600R...
  • Page 14: Terminal Descriptions

    Zone 5 and 13 sensor loop input (+). Common (-) for Zone 5 and 6 sensor loop. ZN 6 Zone 6 and 14 sensor loop input (+). ZN 7 Zone 7 and 15 sensor loop input (+). Bosch Security Systems 10/12 BLCC600R...
  • Page 15: About The Keypad

    Solution 144 Quick Start Guide Abo ut Th e Key p ad Description The keypad has 20 keys that allow you to input instructions The [] key allows you to navigate and navigate the programming menu’s as required. Some through menus or to toggle characters...
  • Page 16: Status Icons / Led's

    Not ready, Zone Open All On Flashing Alarm Area is off. Green Flashing Area not ready to turn on Red & Installer programming mode is Flashing Green active. Table 7: ICON & LED Indicator Meanings Bosch Security Systems 10/12 BLCC600R...
  • Page 17: Keypad & Readers Setup

    Solution 144 Quick Start Guide Key p ad & R ea d er s S e t u p R o tar y Swi tc h Add res s S e l e c t The control panel can have a maximum of 16 keypads and/ Keypads and readers fitted to the system must be assigned or readers connected via the LAN terminals.
  • Page 18: Dtmf Control Functions

    To navigate backwards through the menu items press the [MENU] key at any time. Alternatively if you know the direct menu item number press [MENU] + Item Number. Bosch Security Systems 10/12 BLCC600R...
  • Page 19: Command Menu

    Solution 144 Quick Start Guide Description Characters Assigned To Each Numeric Key  Scrolls Cursor Left &  Scrolls Cursor Right Scrolls Cursor Up  Scrolls Cursor Down  Enter Menu Options or Saves Changes Go Back One Level, Hold Down to Exit...
  • Page 20: Clock Programming

    8. Press and hold down [MENU] to exit. 1. Enter programming mode. [1][2][3][4] + [MENU] 2. Select factory default option. MENU 7-0-4 3. The panel will reset and revert to normal operation when the default is complete. Bosch Security Systems 10/12 BLCC600R...
  • Page 21: Domestic Template Defaults

    Solution 144 Quick Start Guide You can disable factory defaulting using MENU 7-7- Zon e Ar ray 4. If factory defaulting has been disabled you must The feature allows you to view the condition of all zones on Note know the installer code to perform a factory default the panel in banks of 16 zones at a time.
  • Page 22: Output Array

    A complete reporting template is available on the Solution Zn931 - 938 LAN Power Supply 9 - 16 Link CD or from your nearest Bosch security products outlet. Zn951 - 958 Output Expander 9 - 16 Your base station will need to create a specific reporting...
  • Page 23: Menu Reference Table

    Solution 144 Quick Start Guide M e n u R e fe re nce Tab le The Solution Controller includes a simple text menu system which makes all levels of programming extremely easy. Once a valid PIN has been entered followed by the MENU key the system will automatically determine which menus and option the user has access to and only those items will be displayed.
  • Page 24 5-4-3 System Route 5-4-4 Emergency Route 5-4-5 Swinger Dialler 5-4-6 Burg Report Delay 5-4-7 Fire Report Delay MyAlarm 5-5-0 IP Address 5-5-1 IP Port 5-5-2 MyAlarm Options 5-5-7 Gateway Numbers 5-5-8 Email Address 5-5-9 Email Options Bosch Security Systems 10/12 BLCC600R...
  • Page 25: Table 17: Menu Structure And Layout

    Solution 144 Quick Start Guide Devices System IP Reporting Commands Commands 5-6-0 Receiver IP 6-0-0 Device Status 7-0-0 Panel Status 5-6-1 Receiver Port 6-0-1 LAN Secure 7-0-1 System Trouble 5-6-2 Poll Rate 6-0-2 LAN Scan 7-0-2 History Log 5-6-3 ACK Wait Time...
  • Page 26: Program Locations

    Access > RF Keyfob > The following section lists all of the programming locations Add Keyfob MENU 1-3-0 available in the Solution 144. The default values for each Delete Keyfob parameter are shown in grey. MENU 1-3-1 In order to keep the size of this guide down to a minimum...
  • Page 27 Solution 144 Quick Start Guide Access > User Properties > Access > Global Properties > TimeZone Access PIN Length MENU 1-4-4 MENU 1-5-0 (*** System Wide Parameter ***) 00 - Disabled 00 - Variable 03 - 3 Digits 06 - 6 Digits...
  • Page 28: Area Programming

    Use the [] and [] keys to scroll the list of options. Select the option required, then press [ON] or [OFF] to enable or disable. A [] will display to indicate option set. Press [OK] to save when finished. Bosch Security Systems 10/12 BLCC600R...
  • Page 29: Auto Arming

    Solution 144 Quick Start Guide Areas > Properties > Areas > Reporting > Strobe Trigger Account Dest 1 MENU 2-1-5 MENU 2-2-0 0 0 0 0 0 0 0 0 0 0 1 Audible Burglary 2 Silent Burglary Program the area account number for Destination 1 here (Enter digits 0 –...
  • Page 30: Input Programming

    Use the [] and [] keys to scroll the list of options. Select program. the option required, then press [ON] or [OFF] to enable or disable. A [] will display to indicate option set. Press [OK] to save when finished. Bosch Security Systems 10/12 BLCC600R...
  • Page 31: Zone Assignments

    Solution 144 Quick Start Guide Zo n e As si gnm e nt s Zone Assignment Table Address Setting Zone Single or Alarm + Module Zone Numbers Zone Numbers Numbers Tamper EOL With CM705B Number (Single EOL) (Alarm+Tamper EOL) SW1 SW2 SW3 SW4 SW5...
  • Page 32: Zone Default Table

    Zo n e D efa ul t Ta bl e The table below list the default values for all zone parameters in the Solution 144. By default, zones 5 to 16 are set as Instant zones and zones 17 to 144 are set as Not Used. Zones marked as Not Used do not require EOL resistors to be fitted.
  • Page 33: Input Options

    Solution 144 Quick Start Guide Inputs > Global Input Options > Inputs > PGM Input > EOL Value Keyswitch Options MENU 3-4-0 MENU 3-5-0 (*** System Wide Parameter ***) 00 - No EOL 08 - 6k8 Ohm 00 - Disabled...
  • Page 34: Output Programming

    N° Of 1/10 Seconds Output Options Off On Low Battery Guest Control Reserved Monitor Overload Monitor Device Fail Alarm On Device Fail Block If All On Show Status On Keypad Table 21: Output Default Table Bosch Security Systems 10/12 BLCC600R...
  • Page 35: Output Event Types

    Solution 144 Quick Start Guide O u t put Eve nt Ty pe s 00 - Disabled 26 - Entry Timing 52 - Exit Error 01 - Battery Trouble 27 - Exit Timing 53 - Keyfob Function 1 02 - AC Trouble...
  • Page 36: Output Assignments

    Assign to CLI Trigger Table 1 or 2 (0 = Both Tables) Use [] and [] keys to program which Area, User, Zone, Keypad or Access Group Number etc you want the output to follow then press [OK]. Bosch Security Systems 10/12 BLCC600R...
  • Page 37: Output Options

    Solution 144 Quick Start Guide Outputs > Properties > Outputs > Door Properties > Output Options MENU 4-1-5 Door Options MENU 4-2-3 1 Off On Low Battery 1 Hold Off If Area Armed 2 Guest Control 2 Hold Off Auto Unlock...
  • Page 38: Comms Programming

    MENU 5-1-7 Digits # 6 1 # Use [] and [] keys to scroll cursor. Enter [0] – [9] for telephone digits. Use [] and [] to toggle special characters * # and , (Pause). Bosch Security Systems 10/12 BLCC600R...
  • Page 39 Solution 144 Quick Start Guide Comms > Properties > Comms > Properties > Call Attempt Count Country MENU 5-2-0 MENU 5-2-3 (*** System Wide Parameter ***) Enter 0 - 10 then press [OK] to program the maximum call Ln1 AUSTRALIA...
  • Page 40 Use [] and [] keys or enter 0 - 4 + [OK]. Enter single [0] – [9] for digits and use [] and [] to toggle special option only. (*** System Wide Parameter ***). characters - * # and , (pause). Bosch Security Systems 10/12 BLCC600R...
  • Page 41 Solution 144 Quick Start Guide Comms > Reporting Comms > MyAlarm > System Route MyAlarm Options MENU 5-4-3 MENU 5-5-2 00 - Log Events Only 1 Reserved 01 - Dest 1 + Log 2 Reserved 02 - Dest 2 + Log 3 Reserved 03 - Dest 1 &...
  • Page 42 (x10) for both Destination 1 and/or Destination 2. Comms > IP Reporting > ACK Wait Time MENU 5-6-3 0 1 0 Seconds Enter 0 - 255 + [OK] to program the acknowledge wait time in seconds for both Destination 1 and/or Destination Bosch Security Systems 10/12 BLCC600R...
  • Page 43 Solution 144 Quick Start Guide Comms > IP Reporting > Comms > IP Remote Access > SIA IP Prefix IP RAS Options MENU 5-6-8 MENU 5-7-2 1 IP RAS Allowed Digits Account 0 0 0 0 0 0 0 0 0 2 IP RAS Only If Disarmed Dest Nº...
  • Page 44: Device Programming

    30 seconds, or by pressing [OK]. Enter [0] – [9] program. This is the area that will be displayed on the for telephone digits. Use [] and [] to toggle special keypad by default. Characters * # and , (Pause). Bosch Security Systems 10/12 BLCC600R...
  • Page 45 Solution 144 Quick Start Guide All keypads must have a home area programmed to Devices > Keypads & Readers > work correctly. Door Assignment MENU 6-1-7 Note 00 - No Door Assignment Devices > Keypads & Readers > 01 - Door 1 Name...
  • Page 46 A [] will display to indicate option set. Press [OK] 01 - Hardware to save when finished. 02 - Xon-Xoff Use [] and [] keys or enter 0 – 2 to program the serial device flow control, then press [OK] to save. Bosch Security Systems 10/12 BLCC600R...
  • Page 47 Solution 144 Quick Start Guide Devices > GSM/GPRS Module > Devices > GSM/GPRS Module > CLI Trigger Table 1 CLI Trigger Table 2 MENU 6-5-5-0 MENU 6-5-5-1 Digits Digits Phone 1 Phone 1 Digits Digits Phone 2 Phone 2 Digits...
  • Page 48 [ON] or [OFF] to enable or disable. A [] will display to indicate option set. Press [OK] to save when finished. See the ethernet module installation guide for more detailed explaination on installation Note configuring the ethernet module. Bosch Security Systems 10/12 BLCC600R...
  • Page 49: System Programming

    Solution 144 Quick Start Guide Sys te m Pro gra m m i ng System > Clock > Locale System > Commands > MENU 7-1-3 Panel Status MENU 7-0-0 (*** System Wide Parameter ***) 00 - Disabled System Trouble MENU 7-0-1...
  • Page 50 For example if you want the system to disarm at 7.30am you would program 07:30:00 in the stop field. See the full installation manual for more details. Bosch Security Systems 10/12 BLCC600R...
  • Page 51 Solution 144 Quick Start Guide System > TimeZones > System > System Options > TimeZone Options General Options MENU 7-5-3 MENU 7-7-0 1 Invert Period Logic 1 Display LAN Fail 2 Master Edit Allowed 2 Report LAN Fail 3 Reserved...
  • Page 52: Testing The System

    Use the [0] – [9] keys or the [] and [] keys to scroll characters, then press [OK] to save. Press [OFF] to clear text from the current cursor position. System > System Testing > Walk Test All Zones MENU 7-9-0 Battery Test MENU 7-9-1 Bosch Security Systems 10/12 BLCC600R...
  • Page 53: Bosch Security Systems 10/12 Blcc600R

    Solution 144 Quick Start Guide Bosch Security Systems 10/12 BLCC600R...
  • Page 54: Installation Details

    INSTALLED BY: DATE: ACCOUNT N°: PANEL LOCATION: PANEL PHONE N°: CLI ENABLED: N° WIRED ZONES: N° OF USERS: N° RF ZONES: N° OF AREAS: WARRANTY COMMON AREA EXPIRES: USED: USER TRAINING COMPLETED BY: PERSON TRAINED: NOTES: Bosch Security Systems 10/12 BLCC600R...
  • Page 55: Specifications

    1 x Telephone Cable RJ12 6P/4C 1 x Tamper Switch Bracket 1 x Pack PCB Mounting Clips (5 pc/pack) 1 x Product Identification Label Available Separately Solution 144 Installation Manual Part Number BLCC600I Solutionlink (RAS) Software Part Number: SW500B Bosch Security Systems 10/12 BLCC600R...
  • Page 56 Bosch Security Systems 25 Huntingwood Drive Huntingwood, NSW 2128 Australia Phone: +612 9672 1777 Facsimile: +612 9672 1717 © 2012 Bosch Security Systems BLCC600R Issue FTR1.1...

Table of Contents