D1256Rb Programming Requirements; Area Text; D9412Gv4/D7412Gv4/D7212Gv4 V1.Xx And Earlier Versions; Figure 14: Example - Area Text For Fire - Bosch D1255RB Installation Manual

Fire keypads and fire alarm annunciator
Hide thumbs Also See for D1255RB:
Table of Contents

Advertisement

D1255RB/D1256RB/D1257RB | Installation Guide | 4.0
Supervised: Certain local jurisdictions might require supervision of fire system annunciators. If
your area has that requirement, set the supervision to YES for the addresses that use fire alarm
annunciators.
Scope: The D1256RB acknowledges fire alarms and troubles, not burglar alarms and troubles.
Set the scope to include fire areas only.
Area: Program the area number of the fire area(s) as normal.
4.2

Area Text

4.2.1

D9412GV4/D7412GV4/D7212GV4 v1.xx and earlier versions

Figure 14: Example – Area Text for Fire Applications
Area # is On
Area # Not Ready
Area # is Off
Area # Acct is On
Area # is On − PRESS ALARM SIL
Fire area should remain in the OFF state at all times. If the authority level is not programmed
correctly, and the fire alarm area arms, PRESS ALARM SIL shows on the display. Pressing the
[ALARM SILENCE] key silences any alarms(s) and disarms the area.
The idle text, * FIRE SYSTEM *, appears on the display when the area is disarmed.
Area # Not Ready − CHECK FIRE SYS
Most fire alarm areas consist of all 24-hour points and the Area # Not Ready display is not used. If a
controlled point type is used for some type of fire supervision device, and the device becomes off-
normal, CHECK FIRE SYS appears on the fire keypad.
Area # is Off − * FIRE SYSTEM *
This is the normal idle text for the fire keypad and annunciator.
Area # Acct is On − PRESS ALARM SIL
Fire area should remain in the OFF state at all times. If the authority level is not programmed
correctly, and the fire alarm area arms, PRESS ALARM SIL shows on the display. Pressing the
[ALARM SILENCE] key silences any alarms(s) and disarms the area.
The idle text, * FIRE SYSTEM *, appears on the display when the area is disarmed.
10
Area 1
P R E S S
A L A R M
C H E C K
F I R E
* F I R E
S Y S T E M *
P R E S S
A L A R M

D1256RB Programming Requirements

Area 2
S I L
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
S Y S
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
S I L
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Bosch Security Systems B.V. | 2020.03 | F01U011791-02