4-2 Alarms
Table 4-1
Table 4-1
TB1 alarm block description
Pin
A1
Telemetry input #1
B1
Telemetry input #2
C1
Telemetry input #3
ACO (alarm cutoff)
D1
Telemetry input #4
A2
Telemetry input #5
B2
Telemetry input #6
C2
Telemetry input #7
D2
Telemetry input #8
A3
Telemetry input #9
B3
Telemetry input #10
C3
Telemetry input #11
D3
A4
B4
Battery on discharge (BOD)
C4
Fuse alarm (FA)
D4
Low voltage alarm (LVA)
Note 1: The alarms listed in this table are connected on the alarm block TB1 at the factory.
Note 2: All alarms listed are normally open contacts.
Note 3: If there is more than one piece of equipment of the same type, the alarms from that
equipment can be wired in parallel. Alarms wired in parallel maximize the number of alarms that
can be reported.
AN2016 Cabinet User Guide
lists the pin descriptions of the TB1 alarm block
Description
Spare
AC fail alarm
alarm
Rel 1.0 Standard May 1999
Pin
A5
High voltage shut down (HVSD)
B5
Rectifier fail alarm minor (RFA
C5
Rectifier fail alarm major (RFA
D5
Battery distribution panel alarm
A6
Environmental control unit (ECU)
B6
C6
Door intrusion alarm
D6
A7
DDM+ or Soneplex minor alarm
B7
DDM+ or Soneplex major alarm
C7
Soneplex critical alarm
D7
Remote measurement unit (RMU)
A8-B8
C8-D8
A9 to D9
Common (ground)
A10 to D10
Common (ground)
Description
alarm
Min)
Maj)
system alarm
High temp alarm
Spare
alarm
Spare
Spare