3-34 Installation guidelines
Procedure 3-11

Connecting ac power

Use this procedure to connect commercial power to the AN2016 Cabinet. Each
AN2016 cabinet can accept a separately protected 120/240 V ac single phase,
60 Hz circuit with a maximum 100A load. For an illustration of the AC wiring
diagram, see
Requirements
You need the following equipment:
Action
Step
1
2
AN2016 Cabinet User Guide
Figure
3-23.
flat head screwdriver
single phase, 3-wire, 120/240 V ac, 30 A, 60 Hz power source
DANGER
Electrical hazard
Observe all safety precautions as specified by local
building codes and the National Electrical Code (NEC). All
procedures should be performed by a licensed electrician.
If local building codes specify procedures different from
those in this section, follow local codes.
DANGER
Electrical shock hazard
Before installation, the ac grounding electrode system must
be bonded to an ac main service power neutral/ground bus.
Contact your local power company or local practices for
information about codes or restrictions for your
installation.
Action
Install the ac power to the AC load center as outlined in the following
paragraphs.
Open the AC compartment door.
Note 1: If not done previously, route the power and ground wires from the
external commercial power source through the conduit in the base of the AC
compartment (see
Note 2: Pull at least 10 feet of wire beyond the concrete base.
Rel 1.0 Standard May 1999
Figure
3-22).
—continued—