Main Circuit Wiring; Motor And Main Circuit Connections; Configuration Of Main Circuit Terminal Block - YASKAWA GA80U4720ABM Manual

Table of Contents

Advertisement

3.3

Main Circuit Wiring

This section gives information about the functions, specifications, and procedures necessary to safely and correctly
wire the main circuit in the drive.
NOTICE: Damage to Equipment. The drive can fail if users frequently turn the drive ON and OFF with the MC on the power source
side to Run and Stop the drive. Incorrect operation can decrease the service life of the relay contacts and electrolytic capacitors. If
you frequently use the magnetic contactor on the power source side to Run and Stop the drive, it can cause drive failure.
Note:
Soldered wire connections can become loose over time and cause unsatisfactory drive performance.

Motor and Main Circuit Connections

WARNING! Electrical Shock Hazard. Do not connect terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, -, +1, +2, +3, B1, or B2 to the
ground terminal. If you connect these terminals to earth ground, it can cause damage to the drive or serious injury or death.
A - DC bus terminal
B - Connect to the drive ground
terminal.
C - Ground the motor case.
Note:
The location of terminals are different for different drive models.

Configuration of Main Circuit Terminal Block

Use
Table 3.1
to find the correct main circuit terminal block figure for your drive.
Model
2004 - 2042, 4002 - 4023
2056, 4031, 4038
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Figure 3.2 Wiring the Main Circuit and Motor
Table 3.1 Configuration of Main Circuit Terminal Block
Shape of Terminal
European terminal
European terminal
D - Three-Phase Motor
E - Use R, S, T for input power supply.
F - Input Protection (Fuses or Circuit
Breakers)
*1

3.3 Main Circuit Wiring

Figure
Figure 3.3
Figure 3.4
65
3