Televisions Placed Above the Fireplace

The following section gives guidelines to place a television above the fireplace.
IMPORTANT NOTE REGARDING TELEVISIONS AND THIS FIREPLACE
Most television manufacturers instruct the homeowner not to place the television above a heat source like this fireplace. Doing
so may decrease the longevity of the television and negate the warranty. If you do place a television above the fireplace, you
should place a mantel (or build-out) between the fireplace and television (or use a CoolSmart TV Wall™ kit). Follow the
guidelines below to reduce the amount of heat reaching the television. Travis Industries does not take responsibility for any
negative impact to televisions placed near this fireplace.
Min. 1" (26mm)
b
Minimum Dimensions:
(a) Minimum Mantel Height above Base of Fireplace*
(b) Minimum Mantel Depth*
(c) Optional Columns (or Build-Out)
* Minimum mantel depth must be 4"(102mm) to allow heat to dissipate. If using a mantel larger than 4"(102mm),
make sure to adjust the mantel height (a) to meet the mantel clearancer (see mantel requirements on page 41 for
details).
The mantel must extend 2" in front of the television and 1" to both sides.
If you have a television that is greater than 6" deep (including the 1" gap behind), you will need to alter the mantel depth
and height (see the example below).
The television must have a 1" gap to the wall to allow for proper cooling. Any build-out near the television must
maintain a 3" gap to the top and sides to prevent heat from being trapped near the television.
NOTE: The mantel must extend 1"(26mm) in front of the TV and 1"(26mm) to both sides. If you have a TV that is greater than
3" (77mm) deep (including the 1"(26mm) gap behind), you will need to alter the mantel depth and height.
© Travis Industries
Installation
(for qualified installers only)
Min. 1" (26mm) Air Gap Behind TV
Television (TV)
Min. 1" (152mm)
a
Fireplace
Min. 3"
(77mm)
Min. 2" (51mm)
(a)
Height
Above
c
Base of
Fireplace
39" (991mm) with 4" (102mm) mantel depth
4" (102mm)*
Must Meet Side Wall Clearances
(Measured to the side of fireplace ZC-can)
4/21/20 - 1458
Optional Column
or Build-Out
(b) Depth
45" (1143mm)
44" (1118mm)
43" (1093mm)
42" (1067mm)
41" (1042mm)
40" (1016mm)
39" (991mm)
PB42,54,72
IDB01243
PB 72 MV/GSB2/GSR2 Install
IDB01242