IO-Link standard
CPU 1515SP PC2 is based on standard IEC 61131-9.
Use in industrial environments
CPU 1515SP PC2 is designed for use in industrial environments. It meets the following standards
for this type of use:
• Requirements on interference emission EN 61000-6-4: 2007 + A1: 2011
• Requirements on immunity EN 61000-6-2: 2005
Use in mixed areas
Under certain circumstances, you can use the CPU 1515SP PC2 in a mixed area. A mixed
area is used for residential purposes and for commercial operations that do not significantly
impact on residents.
If you want to use the CPU 1515SP PC2 in mixed areas, you must ensure that its radio
frequency interference emission complies with the limit classes of the EN 61000‑6‑3 generic
standard. Suitable measures for observing these limits for use in a mixed area are, for
example:
• Installation of the CPU 1515SP PC2 in grounded control cabinets
• Use of noise filters in the supply cables
An individual acceptance test is also required.
Use in residential areas
Note
CPU 1515SP PC2 not intended for use in residential areas
CPU 1515SP PC2 is not intended for use in residential areas. Using the CPU 1515SP PC2 in
residential areas can affect radio and television reception.
Reference
The certificates for the markings and approvals can be found on the Internet under Siemens
Industry Online Support (https://support.industry.siemens.com/cs/de/en/).
13.2

Electromagnetic compatibility

Definition
Electromagnetic compatibility (EMC) is the ability of an electrical installation to function
satisfactorily in its electromagnetic environment without interfering with that environment.
CPU 1515SP PC2 (F/T/TF)