Table 13-2
RF radiation according to IEC 61000-4-3/NAMUR 21
Electromagnetic RF field, amplitude-modulated
80 to 1000 MHz; 1.0 to 2.0 GHz
10 V/m
80% AM (1 kHz)
• RF coupling
Table 13-3
RF coupling according to IEC 61000-4-6
(10 kHz) 150 kHz to 80 MHz
10 V
80% AM (1 kHz)
150 Ω source impedance
Emission of radio interference
Interference emission of electromagnetic fields in accordance with IEC61000-6-4 (measured at
a distance of 10 m).
Table 13-4
Frequency
30 MHz to 230 MHz
230 MHz to 1000 MHz
Emission of interference via AC supply voltage in accordance with EN 55016.
Table 13-5
Frequency
0.15 to 0.5 MHz
0.5 to 30 MHz
CPU 1515SP PC2 (F/T/TF)
Operating Instructions, 03/2023, A5E42603425-AC
Sinusoidal disturbance variables with RF radiation
Sinusoidal disturbance variables with RF coupling
unmodulated
rms
Interference emission of electromagnetic fields
Interference emission via the AC power supply
13.2 Electromagnetic compatibility
2.0 GHz to 6.0 GHz
3 V/m
Emitted interference
< 40 dB (µV/m)Q
< 47 dB (µV/m)Q
Emitted interference
<79 dB (µV) Q
<66 dB (µV) M
<73 dB (µV) Q
<60 dB (µV) M
Technical specifications
corresponds to degree of se‐
verity
3
corresponds to degree of
severity
3
85

Advertisement