Siemens SIMATIC ET 200SP Manual

Siemens SIMATIC ET 200SP Manual

Digital input module di 8x24vdc st
Hide thumbs Also See for SIMATIC ET 200SP:

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200SP

  • Page 2 ___________________ Preface -6BF00-0BA0) ___________________ Documentation guide ___________________ Product overview SIMATIC ___________________ Wiring up ET 200SP ___________________ DI 8x24VDC ST digital input module Parameters/address space (6ES7131-6BF00-0BA0) ___________________ Interrupts/diagnostics alarms Manual ___________________ Technical specifications ___________________ Parameter data record 07/2014 A5E03574157-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
  • Page 5: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................6 Product overview ............................ 8 Properties ............................8 Wiring up .............................. 10 Terminal assignment ........................10 Schematic circuit diagram ......................11 Parameters/address space ........................12 Parameters ........................... 12 Explanation of the parameters ..................... 14 Address space ..........................
  • Page 6: Documentation Guide

    Documentation guide The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The System Manual and Getting Started describe in detail the configuration, installation, wiring and commissioning of the SIMATIC distributed I/O system.
  • Page 7 Documentation guide Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942). My Documentation Manager The My Documentation Manager is used to combine entire manuals or only parts of these to your own manual.
  • Page 8: Product Overview

    Product overview Properties Article number 6ES7131-6BF00-0BA0 View of the module Figure 2-1 View of the module DI 8×24VDC ST Properties The module has the following technical properties: ● Digital input module with 8 inputs ● Supply voltage L+ ● Sink input (PNP) ●...
  • Page 9 ● Color identification labels ● Reference identification label ● Shield connector See also You will find additional information on the accessories in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Manual, 07/2014, A5E03574157-AC...
  • Page 10: Wiring Up

    The first BaseUnit of an ET 200SP station must be a light-colored BaseUnit. Also keep this in mind during the configuration. See also You will find additional information on the BaseUnit types in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Manual, 07/2014, A5E03574157-AC...
  • Page 11: Schematic Circuit Diagram

    Wiring up 3.2 Schematic circuit diagram Schematic circuit diagram Schematic circuit diagram Figure 3-1 Schematic circuit diagram DI 8×24VDC ST DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Manual, 07/2014, A5E03574157-AC...
  • Page 12: Parameters/Address Space

    Parameters/address space Parameters Parameters for DI 8x24VDC ST The effective range of the parameters depends on the type of configuration. The following configurations are possible: ● Central operation with an S7-1500 CPU ● Distributed operation on PROFINET IO in an ET 200SP system ●...
  • Page 13 Parameters/address space 4.1 Parameters Table 4- 1 Settable parameters and their defaults (GSD file) Parameters Value range Default Configuration Effective range in RUN with configuration software, e.g. STEP 7 (TIA Portal) GSD file GSD file PROFINET IO PROFIBUS DP Diagnostics Disable Module Module...
  • Page 14: Explanation Of The Parameters

    Potential group Specifies that a BaseUnit with voltage supply feed-in is located in this slot (see system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293)). DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Manual, 07/2014, A5E03574157-AC...
  • Page 15: Address Space

    Parameters/address space 4.3 Address space Address space Configuration options The following configurations are possible: ● Configuration 1: Without value status ● Configuration 2: With value status Evaluating the value status An additional byte is allocated in the input address space if you enable the value status for the digital module.
  • Page 16: Interrupts/Diagnostics Alarms

    Interrupts/diagnostics alarms Status and error display LED display The figure below shows the LED displays of the DI 8x24VDC ST. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Figure 5-1 LED display Meaning of the LED displays The following tables show the meaning of the status and error displays. Measures for dealing with diagnostics alarms can be found in the section Diagnostics alarms (Page 19).
  • Page 17 Interrupts/diagnostics alarms 5.1 Status and error display DIAG LED Table 5- 1 DIAG LED fault/error display DIAG LED Meaning Backplane bus supply of the ET 200SP not OK off 
 Module parameters not assigned Flashes Module parameters assigned and no module diagnostics Module parameters assigned and module diagnostics Flashes Channel status LED...
  • Page 18: Interrupts

    Interrupts/diagnostics alarms 5.2 Interrupts Interrupts The DI 8×24VDC ST digital input module supports diagnostic interrupts. Diagnostics interrupt The module generates a diagnostics interrupt for the following events: ● Channel temporarily unavailable ● Short-circuit ● Wire break ● Parameter assignment error ●...
  • Page 19: Diagnostics Alarms

    Interrupts/diagnostics alarms 5.3 Diagnostics alarms Diagnostics alarms A diagnostics alarm is output for each diagnostics event and the DIAG LED on the module flashes. The diagnostics alarms can, for example, be read from the diagnostics buffer of the CPU. You can evaluate the error codes with the user program. Table 5- 4 Diagnostics alarms, their meaning and how to deal with them Diagnostics alarm...
  • Page 20: Technical Specifications

    Technical specifications Technical specifications Technical specifications of the DI 8×24VDC ST 6ES7131-6BF00-0BA0 Product type designation DI 8x24VDC ST General information Firmware version V1.1 Usable BaseUnits BU type A0 Color code for module-specific color identification label CC01 Product function I&M data Engineering with STEP 7 TIA Portal can be configured/integrated as of version V11 SP2 / V13 STEP 7 can be configured/integrated as of version...
  • Page 21 Technical specifications 6.1 Technical specifications 6ES7131-6BF00-0BA0 Power loss Power loss, typ. Address area Address space per module Address space per module, max. 1 byte; + 1 byte for QI information Hardware configuration Fieldbus connection via separate transceiver Digital inputs Number of inputs Input characteristic curve acc.
  • Page 22 0 ℃ Vertical installation, max. 50 ℃ Dimensions Width 15 mm Weights Weight, approx. 28 g Information for market places Digital inputs/outputs, configurable Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/58532597/133300) DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Manual, 07/2014, A5E03574157-AC...
  • Page 23: Parameter Data Record

    Parameter data record Parameter assignment and structure of the parameter data record Parameter assignment in the user program You can change the parameters of the module in RUN. Changing parameters in RUN The "WRREC" instruction is used to transfer the parameters to the module using data record 128.
  • Page 24 Parameter data record A.1 Parameter assignment and structure of the parameter data record Structure of data record 128 Note Channel 0 contains the diagnostics for the entire module. Figure A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Figure A-2 Header information DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0)
  • Page 25 Parameter data record A.1 Parameter assignment and structure of the parameter data record Parameters The figure below shows the structure of the parameters for channels 0 to 7. You enable a parameter by setting the corresponding bit to "1". Figure A-3 Structure byte x to x+1 for the channels 0 to 7 DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Manual, 07/2014, A5E03574157-AC...

Table of Contents