D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN

CC# Assign Door

Default:
Blank
Selection:
1 to 8, Blank
Blank
No door controller is assigned for adding
tokens or the CLOSE DOOR # displays on
the command center.
1 to 8
Assign the door controller that enters the
Add User Mode when initiated. This door
activates the CLOSE DOOR # displays at
this command center if CC Close Door is
Yes.
Program the door number used by this command
center for adding tokens/cards and displaying CC
Close Door.
0101
1. IMPORTANT! 9210 NOT READY
0101
appears at this command center when
0101
you attempt to add a user if a door is
not programmed for this prompt and a
door is not assigned to the area using
the D# Entry Area in the RADAXS
handler. This indicates the control
panel cannot initiate the Add User
Mode until a door is assigned to this
command center.
2. A door does not need to be assigned
to a command center for the user to
control the door(s) using the Door
Control function. Any door that is
active can be controlled by a user who
has the door control authority enabled
at a command center with the doors
area, assigned in the access handler,
within its scope.
During the Add User Mode, token/cards,
door control requests, and RTE/REX does
not function. Put the Door Mode into an
UNLOCKED state before adding users if
there is heavy activity for this door.

CC# Trouble Tone

Default:
Yes
Selection:
Yes or No
Yes
Panel-wide trouble tones sound and
visual displays show at this command
center.
No
Panel-wide troubles do not sound.
Visual displays still show.
Bosch Security Systems | 10/03 | 47775E
Determines whether this command center, or any
command center with the same address setting,
emits the panel-wide trouble tones (power, phone,
SDI bus, and Zonex bus).
Panel-wide trouble tones do not include
Point Troubles, Buzz on Fault, or Close
Door Now.
Assign two CCs to the same area so one
command center emits the tone and
another does not.

CC# Entry Tone

Default:
Yes
Selection:
Yes or No
Yes
This command center sounds entry
tones.
No
This command center does not sound
entry tones.
Determines whether this command center, or any
command center with the same address setting,
emits the Disarm Now entry delay tone. Any Delay
point within the area scope of this command center
initiates the entry sequence.
0101
This prompt allows you to manage the
0101
tone by command center. Entry Tone can
0101
also be turned off when programming your
P## Entry Tone off in Point Index.
Assign two CCs to the same area so one
command center emits the tone and
another does not.

CC# Exit Tone

Default:
Yes
Selection:
Yes or No
Yes
This command center sounds entry
tones.
No
This command center does not sound
entry tones.
Determine whether this command center or any
command center with the same address setting,
emits the Exit Now ### exit delay tone during the
delay arming of an area(s). Any command center
with a scope to arm this area can initiate the exit
tone sequence.
EN | 49