LA 60P-TUR
CAUTION!
The long-term leakage tightness of the entire hydraulic circuit
must be ensured (for example through repeated inspection).
The device is a permanently technically sealed system. In rare
cases, however, leakages may occur on the plate heat ex-
changer due to freezing. The risk is increased in particular in the
event of tampering on the dirt traps, if the requirements for fill-
ing the hydraulic circuit are not complied with, or if the mini-
mum flows are not observed.
CAUTION!
Due to the solubility of propane in water, propane may enter
the hydraulic circuit in the event of leakage at the plate heat
exchanger despite the safety valve and the bubble separator.
CAUTION!
Commissioning, maintenance and repair only by personnel
who have verifiably been trained in dealing with the
refrigerant propane.

9.2 Cleaning the heating system

See the maintenance instructions for the hydraulic station

9.3 Cleaning the air system

See the maintenance instructions

9.4 Maintenance intervals

Maintenance intervals of 6 months must be observed.
www.glendimplex.de
10 Faults / troubleshooting /
repair
This heat pump is a quality product and is designed for trouble-
free operation. In the unlikely event that a fault should occur,
please inform the responsible after-sales service.
CAUTION!
Work on the heat pump must only be performed by
authorised and qualified after-sales service technicians!
NOTE
The repair instructions must be observed.
The following steps must be adhered to before starting the
work
1)
Before starting the work, ensure that the power supply to
the device is disconnected externally.
2)
It is prohibited to remain in the direct vicinity of the device
during storms (risk of lightning)!
3)
Work outdoors on electrical equipment or live components
may only be carried out in dry weather conditions. In wet
conditions (rain, snow etc.), the device must be closed cor-
rectly.
4)
The refrigeration circuit must not be damaged.
5)
The device contains combustible refrigerant. Avoid ignition
sources in the safety zone!
6)
Before opening the device, check the work environment
with a suitable gas detector. Position the gas detector
switched on in the device during all subsequent work.
Carry out a leakage tightness test before switching on the ex-
ternal power supply.
A mobile switch-off device must be mounted before connect-
ing the external power supply (see cap. 3.4 on page X). If there
is a risk of refrigerant escaping during repair work, a mobile ven-
tilation (ex-proof fan) can be used as a supporting or even es-
sential measure.
All repair work must only be carried out by a technician who is
trained in handling flammable refrigerants, has the necessary
experience and fulfils the legal requirements in the relevant
country where the refrigerating system is operated.
Before starting the repair work on the relevant component, the
paint protector must be checked to ensure it is in the original
state. Paint protectors that have to be removed for the repair
work must be mounted again once the work is complete.
Before starting the repair, the system log book must be ob-
served with respect to repairs and modifications already carried
out.
CAUTION!
The leakage tightness of the refrigerant circuit must be tested
after all assembly work is complete and the external power
supply (load and control voltage) has been connected.
CAUTION!
Maintenance and operating instructions for the machine and
the switch box must be taken into account.
CAUTION!
After disconnecting the power supply, you have to wait 5
minutes before all components are de-energised.
452167.66.42 · FD 0008