Procedure; Cleaning / Maintenance; Maintenance; Cleaning The Heating System - Dimplex LA 3860 Installation And Operating Instruction

Air-to-water heat pump for outdoor installation
Table of Contents

Advertisement

LA 3860

7.3 Procedure

The heat pump is started up via the heat pump manager. Ad-
justments should be made in compliance with the instructions.
At hot water temperatures under 7 °C, start-up is not possible.
The water in the buffer tank must be heated to a minimum of
22 °C with the second heat generator.
To ensure a problem-free start-up, the following procedure is to
be implemented:
1)
Close all consumer circuits.
2)
Ensure that the heat pump has the correct water flow.
3)
Select "Winter" mode on the heat pump manager.
4)
In the special functions menu, start the "Start-up" program.
5)
Wait until a return temperature of at least 29 °C has been
reached.
6)
Now slowly reopen the heating circuit valves in succession
so that the heating water flow is constantly raised by
slightly opening the respective heating circuit. The heating
water temperature in the buffer tank must not be allowed
to drop below 24 °C during this process. This ensures that
the heat pump can be defrosted at any time.
7)
When all heat circuits are fully open and a return tempera-
ture of at least 22 °C is maintained, the heat pump start-up
is complete.
CAUTION!
Operating the heat pump at low system temperatures may
cause the heat pump to break down completely.
8

Cleaning / maintenance

8.1 Maintenance

To protect the paintwork, avoid leaning anything against the
device or putting objects on the device. External heat pump
parts can be wiped with a damp cloth and domestic cleaner.
NOTE
Never use cleaning agents containing sand, soda, acid or
chloride as these can damage the surfaces.
To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating sys-
tem cannot be contaminated. In the event that operating mal-
functions due to contamination still occur, the system should
be cleaned as described below.
www.dimplex.de

8.2 Cleaning the heating system

CAUTION!
The installed dirt traps must be cleaned at regular intervals.
The maintenance intervals should be defined according to the
degree of soiling in the system. The filter insert should also be
cleaned.
For cleaning, the heating circuit must be made pressureless in
the vicinity of the dirt trap, the filter compartment unscrewed,
and the filter insert removed and cleaned. Assembly carried out
in reverse order requires attention to correct assembly of the
screen inserts and tightness of the screw joints.
The ingress of oxygen into the heating water circuit may result
in the formation of oxidation products (rust), particularly if steel
components are used. They enter the heating system via the
valves, the circulating pumps and/or plastic pipes. It is there-
fore essential - in particular with respect to the entire pipework
- that only diffusion-resistant materials are used.
NOTE
We recommend the installation of a suitable corrosion
protection system to prevent the formation of deposits (e.g.
rust) in the condenser of the heat pump. We recommend
equipping
electrophysical
system).
Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in
the performance of the liquefier in the heat pump, the system
must be cleaned by a heating technician.
Based on current knowledge, we recommend carrying out the
cleaning with a 5 % phosphor acid or, if more frequent cleaning
is required, with a 5 % formic acid.
In either case, the cleaning fluid should be at room tempera-
ture. We recommend flushing the heat exchanger in the direc-
tion opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating
system circuit, we recommend connecting the flushing device
directly to the flow and return of the liquefier of the heat pump.
It is then important that the system be thoroughly flushed using
appropriate neutralising agents to prevent any damage from
being caused by cleaning agent residue remaining in the sys-
tem.
Acids must be used with care and the regulations of the em-
ployers' liability insurance associations must be adhered to.
The manufacturer's instructions regarding cleaning agent must
be complied with at all times.
452167.66.48-EN · FD 0212
diffusion-open
heating
anti-corrosion
system
English
systems
with
an
(e.g.
ELYSATOR
EN-9

Advertisement

Table of Contents
loading

Table of Contents