Power On And Power Off Problems - Lenovo 7X18 Maintenance Manual

Hide thumbs Also See for 7X18:
Table of Contents

Advertisement

4. If the error recurs with the highest device resource setting (1GB), shutdown the system and remove
some PCIe devices; then, power on the system.
5. If the reboot failed, repeat step 1 to step 4.
6. If the error recurs, press Enter to access System Setup Utility.
7. Select System Settings ➙ Devices and I/O Ports ➙ PCI 64–Bit Resource Allocation, then; modify
the setting from Auto to Enable.
8. If the Boot Device does not support MMIO above 4GB for Legacy Boot, use UEFI Boot Mode or remove/
disable some PCIe devices.
9. DC cycle the system and ensure the system is enter UEFI boot menu or the operating system; then,
capture the FFDC log.
10. Contact Lenovo technical support.
A Lenovo optional device that was just installed does not work.
1. Make sure that:
• The device is supported for the server (see
• You followed the installation instructions that came with the device and the device is installed
correctly.
• You have not loosened any other installed devices or cables.
• You updated the configuration information in system setup. When you start a server and press the
key according to the on-screen instructions to display the Setup Utility. (For more information, see the
"Startup" section in the LXPM documentation compatible with your server at
sysmgt.lenovofiles.com/help/topic/lxpm_frontend/lxpm_product_page.html
other device is changed, you must update the configuration.
2. Reseat the device that you have just installed.
3. Replace the device that you have just installed.
4. Reseat the cable connection and check there is no physical damage to the cable.
5. If there is any cable damages, then replace the cable.
A Lenovo optional device that worked previously does not work now
1. Make sure that all of the cable connections for the device are secure.
2. If the device comes with test instructions, use those instructions to test the device.
3. Reseat the cable connection and check if any physical parts have been damaged, .
4. Replace the cable.
5. Reseat the failing device.
6. Replace the failing device.

Power on and power off problems

Use this information to resolve issues when powering on or powering off the server.
"Embedded hypervisor is not in the boot list" on page 170
"Server does not power on" on page 170
"Server does not power off" on page 171
"Unexpected shutdown with LED not lit" on page 171
"Unexpected shutdown with LED not lit" on page 171
https://static.lenovo.com/us/en/serverproven/index.shtml
https://
.) Whenever memory or any
.
Chapter 4
Problem determination
).
169