14-3 Checking with the EtherNet/IP Status
Indicators on the NX-series
EtherNet/IP Unit
You can check whether an error related to the communications port of the NX-series EtherNet/IP Unit
occurred or not and the error state with the EtherNet/IP status indicators on the NX-series EtherNet/IP
Unit.
Refer to 3-2-1 Operation Status Indicators on page 3-3 for the location of the EtherNet/IP status indi-
cators.
The error state is checked for each communications port. The following flow diagram shows the proce-
dure for checking the error state for a single communications port.
Refer to the NJ/NX-series Troubleshooting Manual (Cat. No. W503) for details on how to identify the
cause of the error and resetting the error using the Sysmac Studio or an HMI.
In addition, refer to Section 6 Device Variables Related to the NX-series EtherNet/IP Unit on page 6-1
for details on device variables related to the NX-series EtherNet/IP Unit.
START
LINK/ACT lit
for relevant port?
Flashing
Lit
NET RUN lit
for relevant port?
Flashing
Lit
NET ERR lit
for relevant port?
Not lit
There are no communications errors in the
relevant port for EtherNet/IP.
*1. You can connect the Sysmac Studio or an HMI to the other port to confirm error details when Ethernet communications are possible for the
other port.
NX-series EtherNet/IP Unit User's Manual (W627)
Ethernet communications are not possible.
To know the detailed error causes, Ethernet
connection *1 through the CPU Unit must be
used to connect to the Sysmac Studio or an
HMI.
Not lit
NET ERR lit
for relevant port?
Not lit
NET ERR lit
for relevant port?
Ethernet communications are possible.
Detailed information on causes
can be checked on the Sysmac
Studio and an HMI connected
through Ethernet.
Flashing
Lit
NET ERR lit
for relevant port?
14 Troubleshooting
If a link is not established with the
Not lit
Ethernet switch connected to the
relevant port, replace the Ethernet
cable or the Ethernet switch.
An error for which recovery is not
possible has occurred in Ethernet
communications of the relevant port.
Lit
To recover Port A, cycle the power
supply to the Controller or replace
the unit.
An Ethernet communications error
has occurred on the relevant port,
however, recovery is possible.
Flashing
Monitor the device variable on the
Sysmac Studio or an HMI connected
through the CPU Unit
the error causes and clear them.
An error for which recovery is not
possible has occurred in CIP
communications or TCP/IP
Lit
application communications on the
relevant port.
To recover the relevant port, cycle
the power supply to the Controller or
replace the unit.
An error for which recovery is possible
has occurred in one of the functions of
Flashing
the relevant port. Use the Sysmac
Studio or an HMI to read the device
variable status to isolate the cause of
the error and correct it.