14 Troubleshooting
Event name
Basic Ethernet Setting Error
Meaning
An Ethernet setting error was detected.
Source
X Bus Ethernet Function Module
Error attributes
Level
Effects
User program
Indicators
Ethernet NET RUN
OFF
Device variable
Variable
ETN_Port1Status.EtnCfgErr
ETN_Port2Status.EtnCfgErr
Cause and cor-
Assumed cause
rection
Parameter error
Power interruption while download-
ing Ethernet port settings
Memory error
Attached infor-
Attached information 1: Error type
mation
01 hex: Non-volatile Memory Access Error, 02 hex: There is an inconsistency in the set values.
Attached information 2: Error Details
00 hex: Non-volatile memory access error, 11 hex: Invalid communications speed setting, 12 hex: Unsupported
communications speed
Precautions/
None
Remarks
14-18
Source details
Minor fault
Recovery
Continues.
Operation
Ethernet NET ERR
Flashes at 1-s intervals.
Data type
BOOL
BOOL
Correction
Identify the cause of the error from
the attached information, correct
the settings, and then download
the settings again.
Please clear all memory or down-
load the settings.
If the above measures do not work,
replace the Unit.
Event code
36010000 hex
1 to 4: Mounting
Detection tim-
position of the X
ing
Bus Unit (unit
number) and
communications
port 1/
communications
port 2 are given
in combination
Automatic re-
Log category
covery, cycle
the power sup-
ply, or Controller
reset
Ethernet communications are not possible for the rele-
vant communications port.
Ethernet LINK/ACT
---
Name
Port1 Basic Ethernet Setting Error
Port2 Basic Ethernet Setting Error
Prevention
None
Do not turn OFF the power supply
to the Controller while downloading
the Ethernet port settings.
None
NX-series EtherNet/IP Unit User's Manual (W627)
At power ON or
Controller reset
System

Advertisement