10 CIP Message Communications
10-5 CIP Object Services
This section shows services that specify the CIP object in the Request Path and access the CIP mes-
sage server function of the NJ/NX-series Controllers.
10-5-1
CIP Objects Sent to the EtherNet/IP Port
The following CIP objects can be sent to an EtherNet/IP port.
Object name
Identity object
TCP/IP interface object
Ethernet link object
10-5-2
Identity Object (Class ID: 01 hex)
This object reads the ID information of the Unit and resets the EtherNet/IP port.
Use the route path to specify the port number (1 or 2) of the EtherNet/IP port to access.
Service Codes
Specify the service to execute with the service code.
Service
Parameter name
code
01 hex
Get_Attribute_All
0E hex
Get_Attribute_Single
05 hex
Reset
Class ID
Specify 01 hex.
10-28
•
Reads ID information from the CPU Unit.
•
Resets the EtherNet/IP port.
•
Writes and reads TCP/IP settings.
•
Makes Ethernet settings and reads the settings.
•
Reads Ethernet status.
Description
Reads the values of the attributes.
Reads the value of the specified attribute.
Resets the EtherNet/IP port.
This parameter is used to reset the EtherNet/IP port when
you change the IP address or other parameter settings and
want to apply them.
Input one of the following values for the ServiceDat input vari-
able to the CIPSend instruction to specify the reset method.
00 hex: Resets the EtherNet/IP port.
02 hex: Clears the saved tag data link settings and resets the
EtherNet/IP port.
Function
NX-series EtherNet/IP Unit User's Manual (W627)
Reference
page 10-28
page 10-32
page 10-35
Supported serv-
ices
Instan-
Classes
ces
Support-
Support-
ed
ed
Support-
Support-
ed
ed
Not sup-
Support-
ported
ed