14 Troubleshooting
Connection status
General
Additional
Status
Status
(hex)
(hex)
01
0116
01
0117
01
011A
01
011B
01
0203
14-58
Source of error
Error code returned from target:
The Major/Minor Revisions did not
match when opening connection.
Error code returned from target:
The tag set specified in the connection's
target variables does not exist.
Error code generated by originator:
Connection could not be established be-
cause the buffer was full due to high traf-
fic.
Error code returned from target:
The RPI was set to a value that is below
the specifications.
Error code generated by originator:
The connection timed out.
Handling
Configuration
Configuration
1
2
Check the ma-
Depends on
jor and minor
the target's
revisions set
specifications.
for the target
(Contact the
device and
target device's
connection. If
manufacturer.)
necessary, ob-
Check that the
tain the most
target device's
recent EDS file
EDS file is cor-
and set it
rect.
again.
Check whether
Depends on
the originator
the target's
and target tag
specifications.
sets and tags
(Contact the
are set correct-
target device's
ly.
manufacturer.)
Unexpected
Unexpected
network traffic
network traffic
may have been
may have been
received.
received.
If there are pla-
If there are pla-
ces where
ces where
broadcast
broadcast
storms occur,
storms occur,
such as loop
such as loop
connections in
connections in
the network
the network
connection for-
connection for-
mat, then cor-
mat, then cor-
rect them.
rect them.
This error does
Depends on
not occur.
the target's
specifications.
(Contact the
target device's
manufacturer.)
Tag data link communications from the target timed
out. Check the power supply and cable wiring of
the devices in the communications path, including
the target and switches. If performance has drop-
ped due to heavy traffic, change the performance
settings. For example, increase the timeout time or
RPI setting.
Also, check whether the CIP message communica-
tions of the target are stopped and whether the CIP
communications are permitted by Packet Filter
function of the originator or the device on the route.
NX-series EtherNet/IP Unit User's Manual (W627)
Configuration
3
Check the orig-
inator's con-
nection set-
tings.
Check the orig-
inator's con-
nection set-
tings. Check
whether the
target tag sets
and tags are
set correctly.
Depends on
the target's
specifications.
(Contact the
target device's
manufacturer.)
Set the origina-
tor's RPI set-
ting to 1 ms or
greater.