2 Specifications and Application Procedures
CIP message
service: Explic-
it messages
CIP Safety rout-
*6
ing
SNMP
EtherNet/IP conformance test
Ethernet interface
*1.
Data will be refreshed at the set interval, regardless of the number of nodes.
*2.
The approximate I/O response time of the tag data link is determined by the relationship between the packet
interval and the number of connections. Refer to 12-3 Tag Data Link I/O Response Time on page 12-23 for
details.
*3.
"pps" means packets per second, i.e., the number of communications packets that can be sent or received
in one second.
*4.
When the Unit is performing tag data link communications where the allowable communications bandwidth
per Unit is close to or greater than 30,000 pps, the following functions may not be used properly. In that
case, use the built-in EtherNet/IP port on the CPU Unit or an EtherNet/IP port of a different NX-series Ether-
Net/IP Unit.
Connecting the Sysmac Studio online from the EtherNet/IP port of the NX-series EtherNet/IP Unit
Connecting the Network Configurator online from the EtherNet/IP port of the NX-series EtherNet/IP Unit
Connecting the NA-series Programmable Terminal online from the EtherNet/IP port of the NX-series
EtherNet/IP Unit
Port forward via the NX-series EtherNet/IP Unit
CIP message communications
SNMP function
These functions of the NX-series EtherNet/IP Unit can be used via X Bus from the built-in EtherNet/IP port
on the CPU Unit or an EtherNet/IP port of a different NX-series EtherNet/IP Unit.
*5.
As the EtherNet/IP port implements the IGMP client, unnecessary multi-cast packets can be filtered by using
an Ethernet switch that supports IGMP Snooping.
*6.
CIP Safety communications and tag data links cannot be used together in one NX-series EtherNet/IP Unit.
2-4
Item
Class 3 (number of connections)
UCMM (non-connec-
Maximum number of
tion type)
clients that can com-
municate at one time
Maximum number of
servers that can com-
municate at one time
Maximum number of routable CIP Safety con-
nections
Maximum routable safety data length per con-
nection
Agents
MIB
NX-EIP201
128 per port
256 total
(clients plus server)
32 per port
64 total
32 per port
64 total
84 total
(originator: 80, target: 4)
32 bytes
SNMPv1 or SNMPv2C
MIB-II
Conforms to CT18.
10BASE-T, 100BASE-TX, or
1000BASE-T
Auto negotiation