Preparing for Operation
Example of Stall Prevention During Operation
Output current
Output frequency
n36
Operation After Recovery from Power Interruption
Setting range
This constant is used to select the processing to be performed after recovery from an
instantaneous power interruption.
Value
0
Discontinues operation.
1
Continues operation only if power interruption is within 0.5 second.
2
Continues operation unconditionally (with no error output).
Note If "1" or "2" is selected to continue operation, the Inverter automatically searches
the motor speed (even when the motor is in a free-running state) and continues
smooth operation. This function is called the speed search function.
Example of Speed Search Function
Motor speed
4-26
0, 1, 2
Free-running state
The output frequency is controlled
so that the Inverter will not stall.
Factory setting 0
Description
Inverter starts operating
Chapter 4
Time
Time
Time