Preparing for Operation
Constant
Dedicated
no.
indicator
n57
n58
n59
n60
n61
n62
n63
n64
n68
n69
Note 1. The upper limit of the setting range and the factory setting for the 400-VAC class
are double the above values.
Note 2. The setting range and factory setting for n31 (electronic thermal reference cur-
rent) depend on the Inverter model. For details, refer to page 4-24.
Normally, set the rated motor amperage in n31.
Note 3. The setting range for the 400-VAC models is "1 to 5."
Note 4. The factory setting for the 3G3EV-A4015-CUE is "3."
Note 5. Displaying the constant no. corresponding to an indicator in the "Dedicated
indicator" column lights the indicator.
Note 6. Constant no. 02 (n02) and subsequent constants can be set only when
constant no. 01 (n01) is set to 1.
Constants in the shaded areas in the above table may not be usable depending on the
PROM number (software version). Use constant no. 69 (n69) to refer to the PROM num-
ber for the models used and make the appropriate settings.
Constant no.
n27
n29
n39
n63
n64
Note "Yes" indicates that the constant can be set.
"No" indicates that the constant cannot be set.
4-12
Description
Jump frequency 2
Jump frequency 3
Jump width
Number of fault retries
Stop Key selection
Slip compensation primary
delay time
UP/DOWN command fre-
quency memory
Operator's frequency set-
ting method
Error history
PROM number (for
manufacturer's reference)
219 or lower
Setting range: 0.5 to 399
Setting range: 0.5 to 10.0
Setting range: 0.10 to 2.00
No
No
Setting range
0.0 to 400
0.0 to 400
0.0 to 25.5
0 to 10
0, 1
0.0 to 25.5
0, 1
0, 1
(Display only)
(Display only)
PROM no. (contents of n69)
Setting range: 0.1 to 399
Setting range: 0.1 to 10.0
Setting range: 0.10 to 2.55
Yes
Yes
Chapter 4
Factory setting
0.0 (Hz)
0.0 (Hz)
1.0 (Hz)
0 (times)
0
2.0
0
0
220 or higher