Preparing for Operation
n24
Maximum Frequency
Setting range
Unit of setting 50.0 to 99.9 (Hz) : 0.1 (Hz)
n25
Maximum Voltage
Setting range
Unit of setting 1 (V)
n26
Maximum Voltage Frequency (Basic Frequency)
Setting range
Unit of setting 1.6 to 99.9 (Hz) : 0.1 (Hz)
Note The values in parentheses are for the 400-VAC class.
•These three constants are used to set a V/f pattern.
•Check the motor specifications and set each constant as follows:
n24: Maximum frequency or rated frequency
n25: Rated voltage
n26: Rated frequency
•The value set in n24 (maximum frequency) must be equal to or greater than the value
set in n26 (maximum voltage frequency). Otherwise, an error will result.
Example of n24, n25, and n26 Settings
Maximum voltage
Output voltage
(V)
4-22
50.0 to 400
(Hz)
100 to 400 (Hz) : 1 (Hz)
1 to 255 (510)
(V)
1.6 to 400 (Hz) Factory setting 60.0 (Hz)
100 to 400 (Hz) : 1 (Hz)
(24 V)
Maximum voltage
frequency (basic
frequency)
Factory setting 60.0 (Hz)
Factory setting 200 (400) (V)