Appendix A
Constant
Indi-
no.
cators
n32
n33
n34
n35
n36
n37
n38
n39
n40
n41
n42
Description
Electronic
0: Standard motor with standard ratings
thermal
1: Standard motor with short-time
protection
2: Dedicated motor with standard ratings
3: Dedicated motor with short-time
4: No thermal protection
Stall prevention
0: Stall prevention
during
deceleration
1: No stall prevention
Stall prevention
30 to 200 (%)
level during
(Based on the rated inverter current as
acceleration
100 percent)
Stall prevention
30 to 200 (%)
level during
(Based on the rated inverter current at
operation
100 percent)
0: Discontinues operation.
Operation after
recovery from
instantaneous
1: Continues operation only if the power
power
interruption
2: Continues operation unconditionally.
Carrier
1: 2.5 (kHz) (see note 2)
frequency
2: 5 (kHz)
3: 7.5 (kHz)
4: 10 (kHz)
Automatic
0.0 to 3.0
torque boost
gain
Frequency
0.10 to 2.55 (times)
reference gain
Frequency
–99 to 99 (%)
reference bias
Frequency
0 to 110 (%)
reference upper
limit
Frequency
0 to 110 (%)
reference lower
limit
Setting range
ratings
ratings
interruption is within 0.5 second.
Chapter 7
Setting
[170]
[160]
[1.0]
[1.00]
[0]
[100]
[0]
7-13