Design
H Wiring on the Output Side of Main Circuit
D Connecting the Terminal Block to the Load
Connect output terminals U, V, and W to motor lead wires U, V, and W, respectively.
D Never Connect Power Supply to Output Terminals
Caution Never connect a power supply to output terminals U, V, and W.
If voltage is applied to the output terminals, the internal mechanism of the
Inverter will be damaged.
D Never Short or Ground the Output Terminals
Caution If the output terminals are touched with bare hands or the output wires come
into contact with the Inverter casing, an electric shock or grounding will occur.
This is extremely hazardous. Also, be careful not to short the output wires.
D Do Not Use a Phase Advance Capacitor or LC/RC Noise Filter
Never connect a phase advance capacitor or LC/RC noise filter to the output circuit. Do-
ing so may result in damage to the Inverter or cause other parts to burn.
D Do Not Use an Electromagnetic Switch
Do not connect an electromagnetic switch or magnetic contactor to the output circuit. If a
load is connected to the Inverter during operation, an inrush current will actuate the
overcurrent protective circuit in the Inverter.
D Installing a Thermal Relay
This Inverter has an electronic thermal protection function to protect the motor from
overheating. If, however, more than one motor is operated with one Inverter or a multi-
polar motor is used, always install a thermal relay (THR) between the Inverter and the
motor and set to "0.0" (no thermal protection) for constant No. 31 ("THR" indicator).
In this case, program the sequence so that the magnetic contactor on the input side of
the main circuit is turned off by the contact of the thermal relay.