7.12 Feeder pump operation

In system Anl 3.0, the feeder pump UP1 only starts to operate in the default setting when a
flow temperature demand of a secondary controller exists.
If CO7 -> F14 - 1 is configured in the primary controller in addition to CO7 -> F15 - 1, the
function is also active when the controller's own secondary circuit requires heat.
Function
Send maximum flow set point

7.13 Locking manual level

To protect the heating system, this function can be used to lock manual level. When this func-
tion has been activated, automatic mode is started when the rotary switch is set to
Function
Locking manual levels

7.14 Locking the rotary switches

When this function has been activated, the controller remains in automatic mode regardless
of the rotary switch positions. The rotary switches can no longer be used to adjust the con-
troller settings.
Function
Locking the rotary switches
88
EB 5575 EN
WE
Configuration
0
CO7 -> F14 - 1
5
Register no. / 5 to 64
WE
Configuration
0
CO5 -> F21 - 1
WE
Configuration
0
CO5 -> F22 - 1
.