Menu Path
Parameter
Standardize
StandardFactor
Params & Display>
BurnerControl>
Configuration>
Config FlameDet>
FlameSignal
FlameSig QRI_B
FlameSigION
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
Sets a datum for a "normal" flame, so that a "normal" flame can be displayed as 100% flame signal on the
OperationalStat screen. If a 82.3% flame is present and the flame standarization is performed, what was
displayed as 82.3% is now displayed as 100%
It does not actually affect when, the LMV will lockout due to a poor flame signal.
This re-datum operation should be performed when a stable, normal flame exists at the burner.
O
Normally this value does not need to be adjusted.
Can be viewed to see what raw flame signal will result in 100% flame,
being displayed on the 'OperationalStat' screen. If the flame signal is not stanandardized, XXXX % will be
displayed indicating that the raw signal is the displayed signal.
The LMV will lock out on low flame signal at about 16% raw flame signal. Standardization does not affect the
lockout point.
This can be viewed to see what raw flame signal (in %) is being sent to the LMV
by the flame scanner. This parameter only exists on the LMV52.
The LMV will alarm when this value is less than about 16%.
This signal refers to INPUT terminals X10-01.01 or (X10-02.02)
Not adjustable
Not adjustable.
U
This can be viewed to see what raw flame signal (in %) is being sent to the LMV by the ionization probe
(flame rod) or UV sensor on terminal X10-03.01. This parameter only exists on the LMV52.
The LMV will alarm when this value is less than about 16%.
Not adjustable.
Flame signal range is 0-100%
Flame failure is at 16% (raw)
Extraneous light is at 4% (raw)
Sec 4 Pg 31
Descriptions / Notes
40-70
All