Error
Diag.
Device
Display
code
code
9B
9C
9E
A0
A1
Internal Fault
Load Controller
A2
A3
A4
A5
A6
Inadmissible
A7
Selection aux
Sensor Cold Start
B0
B1
B2
LMV5
B4
Load
A6
B5
Cont.
B6
Mod.
B7
B8
B9
BA
Internal Fault
BB
Load Controller
BC
BD
C0
E0
E1
E2
EA
EB
EC
ED
LMV5 QSG Rev 4
Meaning for the LMV5x system
Fault with Base Unit (LMV5) Internal Load Controler
Fault PageAccess, invalid access status
Fault voltage monitor test
Fault during readout of PDO message
XP smaller than min. value
XP larger than max. value
TN smaller than min. value
TN larger than max. value
TV smaller than min. value
TV larger than max. value
Parameter outside the permissible range
Inadmissible selection of the auxiliary sensor
Red/Inv fault with float variables
Red/Inv fault of a Red/Inv variable
Fault during key value check
Fault in fault routine
Step to invalid interrupt vector
Time block too long: Time block 0
Time block too long: Time block 1
Time block too long: Time block 2
Time block too long: Time block 3
Time block too long: Time block 4
Time block too long: Time block 5
Time block too long: Time block 6
Time block too long: Time block 7
CRC fault in page
Identpower
Controller parameter KP
Scanning time
Invalid branch in eeprom module()
Invalid branch in eeprom module()
Invalid branch in eeprom module()
Invalid branch in eeprom module()
Sec 5 Pg 37
Corrective action
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5
When using the auxiliary temperature sensor for cold
start, a temperature sensor must be selected at input 1
or 4
If fault occurs sporadically improve EMC. If fault occurs
continously, replace LMV5