Siemens LMV5 Quick Start Manual page 169

Hide thumbs Also See for LMV5:

Advertisement

Error
Diag.
Device
Display
code
code
Unplaus Value
23
Ri 02 Measuring
Response Time
24
Measuring Cell
too long
O2 Sensor Test
25
aborted by O2
AB
PLL5..
Module
30
31
32
33
Internal Fault O2
34
Module
38
3E
3F
Any #
B0
01
Internal Fault
LMV5..
Basic Unit
02
B1
01
LMV5 QSG Rev 4
Meaning for the LMV5x system
Fault with 02 Module (PLL5..) or Oxygen Sensor (QGO2..)
Measured internal resistance of the QGO measuring cell
is smaller than 5 Ohm or greater than 150 Ohm
Cell
Measured response time of the QGO measuring cell
O2
exceeds 5 seconds
(completely electronic)
Fault occurred during O2 sensor test
CAN fault
CRC fault of a parameter page
Page too long open
Page disrupted
Invalid access to parameters
Fault during copying of a parameter page
External plausibility fault. This type of fault covers possible
faults occurring due to invalid presettings in the drive
commands. In response, the presettings will be ignored.
Internal plausibility fault. This type of fault detects faults that
cannot practically occur...
Fault with Base Unit (LMV5)
Fault during test of port outputs
Fault when resetting the set outputs
Fault during ZR test
Fault during short-circuit test between inputs and outputs
Sec 5 Pg 43
Corrective action
1) Check the wiring between the O2 Module and the O2
sensor.
2) O2 Sensor may have reached the end of its service
life (Check Resistance through AZL) If greater than 140 -
150 ohms, replace sensor.
1) Check mounting position / oirentation of O2 sensor.
2) Check to see if O2 sensor is dirty. Do Not blow out
with compresed air when hot! Cool, then blow out with
low pressure compressed air.
3) O2 Sensor may have reached the end of its service
life (Check Resistance through AZL) If greater than 140 -
150 ohms, replace sensor.
Check (through the AZL) to see if the measured O2
value is fluctuating.
1) If fault occurs sporadically: Improve EMC.
2) If fault occurs constantly: Replace PLL5..
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
4) Replace the LMV5
1) If fault occurs sporadically: Improve EMC.
2) If fault occurs constantly: Replace LMV5
www.scccombustion.com