Reply time of AZL... to a message from the master
Note
Modbus functions
LMV5 QSG Rev 4
1. Reading data from the LMV5... system:
1...3 addresses
25...75 ms
4...9 addresses
75...125 ms
10...15 addresses
125...175 ms
16...20 addresses
175...225 ms
These periods of time are defined from the complete writing of the message from the mas-
ter to sending the first byte by the AZL...
2. Writing data to the LMV5... system:
1 address
25...75 ms
2...3 addresses
75...125 ms
4...5 addresses
125...175 ms
6 addresses
175...225 ms
The following Modbus functions are supported:
Function number
03 / 04
06
16
For more information about the Modbus protocol, refer to www.modbus.org.
Sec 8 Pg 4
Function
Reading n words
Writing 1 word
Writing n words
www.scccombustion.com