The following steps outline the procedure for installing the ACS450 software on a PC.
This procedure is valid for AZL5 software up to, and including version 4.20.
1) If installing from an email attachment, or a series of email attachments, ensure that the
following files are in the same folder on your computer: (If using the CD, skip to step 2.)
2) Click on the setup.exe file. This should start the installation. Pick the desired options as
the installation prompts.
3) After the installation is complete, most of the files necessary for the ACS450 should be
on the computer under C:\Program Files\ACS450. Notice that there are files such as
para_nr_0170.cod in this directory. On some software installs (older versions), these
.cod files only go up to para_nr_0390.cod. If the latest version of software is installed,
the .cod files will go up to para_nr_0450.cod.
4) If the files only go up to 0390.cod some additional .cod files are necessary so that the
ACS450 is compatible with the latest AZL5 software. Copy and paste the additional,
necessary .cod flies under C:\Program Files\ACS450.
5) At this point, the ACS450 is ready to run. The first time ACS450 is started it will prompt
for a license code. When prompted, type the following license code: 041028000703GH.
6) Next, the PC can be connected to the AZL5 through the RS232 (9 pin) port on the front
of the AZL5 (under the small plastic door). If the computer has a serial port a male to
female 9 pin (commonly referred to as RS232) null modem cable is needed to connect
the computer to the AZL5. A plain male / female cable could also be used with a null
modem adapter. If the computer only has USB ports available, a USB to serial adapter
will be necessary with a null modem adapter on the 9 pin end of the USB to serial
adapter.
7) In order to connect, the AZL5 must be put into InterfacePC mode. This selection is found
under the AZL5 menu: Operation > Optgmodeselect > InterfacePC.
8) Once the AZL5 is in interface mode, attempt to connect with the ACS450 on the user
level. If the connection is successful, then this means that the cord connections are
correct and the com ports are assigned correctly. If the connection is not successful on
the user level, check the connection cord and / or try to use a different com port. The
com port for the ACS450 can be changed under the ACS450 drop down menu,
System LMV5x > Options.
9) After the connection at the user level is successful, disconnect from the AZL5 and then
reconnect at the service or OEM level, if desired. Remember that a password will be
necessary to access the LMV5 on a service or OEM level, and that the password is case
sensitive.
Note: If a fault window appears, it is not necessary to close the fault window. It can be
moved to the side and temporarily ignored. Most tasks, such as saving parameter
sets, can be done with the fault window open. If the fault window is closed and the
fault is not cleared, the fault window will reappear in a few seconds.
LMV5 QSG Rev 4
Installation and Set-up Procedure 9-2
Sec 9 Pg 2
www.scccombustion.com