Siemens LMV5 Quick Start Manual page 166

Hide thumbs Also See for LMV5:

Advertisement

Error
Diag.
Device
Display
code
code
Communication
40
AZL with PC tool
A7
88
89
AZL
Internal Fault AZL
8A
AZL
Any #
01
02
04
05
07
Internal Fault
08
VSD Module
09
LMV5
A9
0A
VSD
module
0C
Alarm from VSD Fault has been triggered by the VSD.
LMV5 QSG Rev 4
Meaning for the LMV5x system
Fault with AZL5...
Parameterization fault PC tool. Disclosed by key value check in
AZL
RAM fault with redundant inverse variables
Program run fault, execution of program code that will probably
never be executed
Unintentional watchdog reset
Fault with Base Unit (LMV5) VSD Module
CRC fault during ROM test
CRC fault during RAM test
Fault during key value check
Error code for time block overflow
Sync fault or CRC fault
Error code for main loop counter
Fault during stack test
Max IRQ speed reached
Sec 5 Pg 40
Corrective action
Check cable between AZL and PC. A null modem
adapter must be used on the 9 pin connector if the cable
does not have this internally. A USB to serial adapter is
OK to use when connecting the AZL to a laptop.
1) If fault occurs sporadically: Improve EMC.
2) If fault occurs constantly: Replace AZL5...
1) If fault occurs sporadically: Improve EMC.
2) If fault occurs constantly: Replace LMV5
1) Possibly interference on the line to the speed sensor,
check cable routing, use shielded cable.
2) If fault occurs sporadically: Improve EMC.
3) If fault occurs constantly: Replace VSD Module.
1) This indicates that a fault has been relayed to the
LMV5 from the VSD via the VSD alarm input terminal.
This indicates a fault in the VSD, not the LMV5. Thus,
check the VSD error codes and take action based on
those codes.
2) Check VSD settings (ramps, motor settings),
increase ramp time on VSD and basic unit, if necessary.
3) Check Motor and VSD for proper sizing.