Menu Path
Parameter
OilPressureMin
OilPressureMax
Params & Display>
HeavyOilDirStart
BurnerControl>
Configuration>
ConfigIn/Output
Start/PS-Valve
ReacExtranLight
Params & Display>
BurnerControl>
Configuration>
Config FlameDet
ExtranLightTest
LMV5 QSG Rev 4
U = User
O = OEM
S = Service
Activates or deactivates (INPUT X5-01.02) for a low oil pressure switch.
If this is set to (act from ts) the LMV will look for this switch to be made in phase 40.
When set to (activated), the LMV will look for the switch to be made in phase 38.
Def = Activated
Activates or deactivates INPUT X5-02.02 as a input for the high oil pressure switch.
O
Def = Activated, Typ = Deactivated
This activates or deactivates INPUT X6-01.03 for a Heavy Oil Stage release contact.
If this terminal has power, it releases the LMV for stage 2 heavy oil. Not intended for running interlocks, such
as oil temperature. Def = activated, however this setting has no effect unless HOgp (Heavy Oil with a gas
pilot) fuel train is configured.
Setting controls the behavior of OUTPUT terminal X4-03.03. Def / Typ = StartSignal
StartSignal mode, X4-03.03 energizes in phase 21 with the fan,
as would be suited to open an outside air damper or stack damper.
Note: If ContinuousPurge is activated, this terminal will be energized as long as the fan in running.
S
PS Relief mode, this output energizes a 3-way valve, used to check the fan air press switch.
,
p
The valve is energized, venting the air press switch to atmosphere during Phase 79.
PS Relief_inv mode, this output energizes a 3-way valve, used to check the fan air press switch.
The valve is energized, exposing the air press switch to fan pressure in every phase except Phase 79.
Setting determines what action the LMV should take in the event of a unexpected flame signal.
The LMV does not expect to "see" a flame when the pilot valve, and the main fuel valves are closed.
The LMV will also ignore a flame signal for the afterburn time.
If a flame is seen other than at these times, provided that the extraneous light test is activated then either a
O
startblock or a lockout will occur, depending upon this setting. Def / Typ= Startblock
Activates or deactivates the extraneous light check during the start sequence and during standby. NOTE :
This setting is intended to be used with applications such as waste incinerators. DO NOT deactivate
for boiler burners. Def = Activated
Sec 4 Pg 30
Descriptions / Notes
g
y
,
38
-
62
22-62
38
21
-
30
or
p
79
70
All